Standard Event Reports, Sag/Swell/Interruption Report, and SER
SEL-351 Instruction Manual
12-5
Table 12.2: Event Types
Event Type
Description
AG, BG, CG
Single phase-to-ground faults. Appends T if TRIP asserted.
ABC
Three-phase faults. Appends T if TRIP asserted.
AB, BC, CA
Phase-to-phase faults. Appends T if TRIP asserted.
ABG, BCG, CAG
Two phase-to-ground faults. Appends T if TRIP asserted.
TRIP
Assertion of Relay Word bit TRIP (fault locator could not
operate successfully to determine the phase involvement, so
just TRIP is displayed).
ER
SEL
OGIC
Control Equation setting ER. Phase involvement is
indeterminate.
TRIG
Execution of TRIGGER command.
PULSE
Execution of PULSE command.
The event type designations AG through CAG in Table 12.2 are only entered in the “Event:” field
if the fault locator operates successfully. If the fault locator does not operate successfully, just
TRIP or ER is displayed.
Fault Location
The relay reports the fault location if the EFLOC setting = Y and the fault locator operates
successfully after an event report is generated. If the fault locator does not operate successfully,
$$$$$$ is listed in the field. If EFLOC = N, the field is blank. Fault location is based upon the
line impedance settings Z1MAG, Z1ANG, Z0MAG, and Z0ANG and corresponding line length
setting LL. For delta-connected voltages, additional zero-sequence source impedance settings
Z0SMAG and Z0SANG are required so that zero-sequence voltage can be derived for fault
locating. See the SET command in Table 9.1 and corresponding Settings Sheet 1 of 22 in
Section
9: Setting the Relay
for information on the line parameter settings.
Targets
The relay reports the targets at the rising edge of TRIP. The targets include: INST, COMM,
S0TF, 50, 51, and 81. If there is no rising edge of TRIP in the report, the Targets field is blank.
See
Front-Panel Target LEDs
in
Section 5: Trip and Target Logic
.
Currents
The “Currents (A pri), ABCNGQ:” field shows the currents present in the event report row
containing the maximum phase current. The listed currents are:
Phase (A = channel IA, B = channel IB, C = channel IC)
Neutral ground (N = channel IN)
Calculated residual ((I
G
= 3I
0
; calculated from channels IA, IB, and IC)
Negative-sequence (Q = 3I
2
; calculated from channels IA, IB, and IC)
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...