4-30
Loss-of-Potential, Load Encroachment, and Directional Element Logic
Date Code 20001006
SEL-351 Instruction Manual
-128.00 to 128.00
W
secondary (300 V voltage inputs, VA, VB, VC; 5 A nominal phase
current inputs, IA, IB, IC)
-640.00 to 640.00
W
secondary (300 V voltage inputs, VA, VB, VC; 1 A nominal phase
current inputs, IA, IB, IC)
Z2F and Z2R are used to calculate the Forward and Reverse Thresholds, respectively, for the
negative-sequence voltage-polarized directional elements (see Figure 4.8 and Figure 4.14).
Z2F and Z2R Set Automatically
If enable setting E32 = AUTO, settings Z2F and Z2R (negative-sequence impedance values) are
calculated automatically, using the positive-sequence line impedance magnitude setting Z1MAG as
follows:
Z2F = Z1MAG/2
(
W
secondary)
Z2R = Z1MAG/2 + z
(
W
secondary; “z” listed in table below)
If enable setting E32 = Y, settings Z2F and Z2R (negative-sequence impedance values) are
calculated by the user and entered by the user, but setting Z2R must be greater in value than setting
Z2F by value “z”:
Relay Configuration
z (
W
secondary)
5 A nominal current, 150 V voltage inputs
0.1
5 A nominal current, 300 V voltage inputs
0.2
1 A nominal current, 150 V voltage inputs
0.5
1 A nominal current, 300 V voltage inputs
1.0
50QFP – Forward Directional Negative-Sequence Current Pickup
50QRP – Reverse Directional Negative-Sequence Current Pickup
Setting Range:
0.25 - 5.00 A secondary (5 A nominal phase current inputs, IA, IB, IC)
0.05 - 1.00 A secondary (1 A nominal phase current inputs, IA, IB, IC)
The 50QFP setting (3I
2
current value) is the pickup for the forward fault detector 50QF of the
negative-sequence voltage-polarized directional elements (see Figure 4.5). Ideally, the setting is
above normal load unbalance and below the lowest expected negative-sequence current magnitude
for unbalanced forward faults.
The 50QRP setting (3I
2
current value) is the pickup for the reverse fault detector 50QR of the
negative-sequence voltage-polarized directional elements (see Figure 4.5). Ideally, the setting is
above normal load unbalance and below the lowest expected negative-sequence current magnitude
for unbalanced reverse faults.
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...