TROUBLESHOOTING
Inspection Procedure
Complete the following procedure before disturbing the system. After you finish the inspec-
tion, proceed to the Troubleshooting Table.
1.
Measure and record control power voltage at terminals 44 and 45.
2.
Check to see that the power is on, but do not turn system off if it is on.
3.
Measure and record the voltage at all control inputs.
4.
Measure and record the state of all output relays.
5.
Inspect the cabling to the serial communications ports and be sure a communications
device is connected to at least one communications port.
Troubleshooting Table
All Front Panel LEDs Dark
1.
Power is off.
2 .
Blown fuse.
3.
Input power not present.
4.
Self test failure.
5.
Target command improperly set.
Note:
For 1, 2, 3, and 4 the ALARM relay contacts should be closed.
System Does Not Respond to Commands
1.
Communications device not connected to system.
2.
Relay or communications device at incorrect baud rate or other communication parameter
incompatibility, including cabling error.
3.
System is processing event record. Wait several seconds.
Date Code 931227
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-43
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...