S
ETTINGS
S
HEET
Page
13
OF
14
FOR THE
SEL-2100
Date
S
ERIAL
P
ORT
S
ETTINGS
(S
ERIAL
P
ORT
C
OMMAND
SET P)
Date Code 20010529
Settings Sheets
H-13
SEL-2100 Instruction Manual
Port setting information not described elsewhere in this instruction manual:
Minutes to Port Time-Out:
Set T_OUT to the number of minutes of serial port inactivity for
an automatic log out. Set T_OUT = 0 for no port time-out.
Number of Lines in Terminal:
Set TLINES to the number of lines displayed on the terminal
before the “Press RETURN to continue” prompt is displayed and line scrolling is paused. Set
TLINES = OFF for line scrolling without pauses.
Send Auto Messages to Port:
Set AUTO = Y to enable AUTO messages on the serial port.
Automatic messages are ASCII messages sent to the port to indicate a power on condition or
status failure without a user request. Set AUTO = N to disable AUTO messages.
Fast Operate Enable:
Set FASTOP = Y to enable binary Fast Operate
messages on the serial
port. Refer to
Appendix E: Fast Meter Protocol
for a description of Fast Operate commands.
Set FASTOP = N to disable this feature.
Port Number (1—16)
Port =
Protocol = DNP
Refer to
Appendix C
for more details about DNP V3.00 protocol.
Protocol Setting
PROTO = DNP
Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400)
SPEED =
DNP Address (0–65534)
DNPADR =
Class for Binary Event Data (0–3)
CLASSB =
Class for Counter Event Data (0–3)
CLASSC =
Minutes for Request Interval (0–32767)
TIMERQ =
Seconds to Select/Operate Time-Out (0.0–30.0)
STIMEO =
Data Link Retries (0–15)
DRETRY =
Seconds to Data Link Time-Out (0–5)
DTIMEO =
Minimum Seconds from DCD to Tx (0.00–1.00)
MINDLY =
Maximum Seconds from DCD to Tx (0.00–1.00)
MAXDLY =
Settle Time from RTS ON to Tx (OFF, 0.00–30.00 sec)
PREDLY =
Settle Time from Tx to RTS OFF (0.00–30.00 sec)
PSTDLY =
Seconds to Event Message Confirm Time-Out (1–50)
ETIMEO =
Enable Unsolicited Reporting (Y, N)
UNSOL =
Enable Unsolicited Reporting at Power-up (Y, N)
PUNSOL =
DNP Address to Report (0–65534)
REPADR =
Number of Events to Transmit On (1–200)
NUMEVE =
Seconds Until Oldest Event to Tx On (0.0–60.0)
AGEEVE =
Summary of Contents for SEL-2100
Page 6: ......
Page 8: ......
Page 10: ......
Page 26: ......
Page 36: ......
Page 38: ......
Page 62: ......
Page 64: ......
Page 94: ......
Page 104: ......
Page 118: ......
Page 120: ......
Page 124: ......
Page 126: ......
Page 136: ......
Page 138: ......
Page 144: ......
Page 146: ......
Page 150: ......
Page 164: ......
Page 168: ......
Page 178: ......