5.2 Set up the parameters
To set up the parameters please hold
the
DISP
button for about 3 seconds.
The „Par” symbol appears for a short
time.
The
parameters
can
be
selected with the
SEL
button.
Threshold value for second-stage:
0.5...3.0 °C / 1.0...5.5 ºF. Only in two-stage mode; in single-
stage mode: --.--
Integration time: 10…99 minutes Only in two-stage or
modulation mode, in single-stage mode, or in off-state
(--.--) appears. Setting it lower than 10 will result in off-state
of integration.
Hysteresis , can be activated by
0.2…2.0 °C / 0.4...3.6 ºF
Sensor correction: if the sensor could not be mounted at an
optimal place, the measured temperature can be offset:
-9.9..+10.0 °C / -9.9..+10.0 ºF
t1: After starting the heater, it runs with full power until it
stops at the programmed time, in this case: 0…5 minute.
t2: For the displayed time, the heater stops completely
(5..60 Sec). It only appears, if the t1 is not equal to zero.
Ability of a restart:
t3: The heater starts with full load for 1 minute, afterwards
the controller switches to the regular mode (0: off). It does
not appear unless the two-stage control is selected.
Proportional range: 1.5...10.0 °C / 2.7...18.0 ºF.
The modulated output is spread across this range.
Only in modulation mode; in single-stage mode: --.--.
Output precentage of the heater in first-stage.
Only effects the displayed value.
In single-stage mode (--.--) appears.
Summary of Contents for ThermoControl Plus 4M
Page 22: ... 22 6 4 Wiring connections ...
Page 23: ... 23 ...
Page 28: ... 28 8 Appendix Wiring diagram ThermoControl Plus 4M 1 8 Zones single stage luminous heater ...
Page 29: ... 29 Wiring diagram ThermoControl Plus 4M 1 4 Zones two stage luminous heater ...
Page 30: ... 30 Wiring diagram ThermoControl Plus 4M 1 8 Zones single stage radiant tube heater ...
Page 31: ... 31 Wiring diagram ThermoControl Plus 4M 1 4 Zones two stage radiant tube heater ...
Page 32: ... 32 Wiring diagram ThermoControl Plus 4M 1 4 Zones modulation radiant tube heater ...