schwankgroup.com/schwankair
SchwankAir Controller
Possibility of making general settings that are also
in the Start-up wizard and execute user reset.
Change the date, time, language and
temperature unit.
General settings
>Installer menu
External control
General settings
Support menu
>Installer menu>General settings
Set date
Set time
Set language
Function test
To test the fan and heating steps, run the
function test.
>Installer menu>General settings
Set temp. unit
Function test
Factory reset
>Installer menu>General settings
Function test
Start test
►
Skip test
>Installer menu>General settings
Function test
Test completed
►
Restart test
>Installer menu>General settings
Fan step 1-5
Heating step off-1
Factory reset
Resets values to factory settings.
>Installer menu>General settings
Function test
Factory reset
Manual system check
Function test
Factory reset
Manual system check
>Installer menu>General settings
Manual system check
Run Manual system check, if required or
after physical alteration of system, to identify
connected units and sensors.
Alarm and error codes
The control has different alarms and error codes
for safe and problem free operation.
If alarms or error codes have been indicated
these must be reset in order to return to normal
operation, for example activating the heating
again. Fan mode is active even when, for
example, the over heating alarm has been
indicated.
Displaying alarm and error codes
In event of alarm or error the alarm/error code
is shown in the status window. In event of alarm/
error code the unit it applies to is displayed.
See Table - Alarms and Table - Error codes
[Quick Guide].