Fuses
It is recommended that the following fuses for protecting the equipment and subject to local
authority:
For 220-240 VAC use a fast blow fuse rated 5 Amps.
For 110-120 VAC use a fast blow fuse rated 10 Amps.
Thermal Limiting
The Fan System is designed to monitor motor and controller temperatures and, in the event, that
operating temperatures exceed control limits, fan speed will automatically reduce until the system is
within temperature limits. No user intervention is required.
Electrical Safety
Never work on the drive, motor cable or motor when input power is applied. After disconnecting the
input power, always wait for 5 minutes to let the intermediate circuit capacitors discharge before you
start working on the drive, motor or motor cable.
Do not work on the control cables when power is applied to the drive or to the external control
circuits. Externally supplied control circuits may carry dangerous voltage even when the input power
of the drive is switched off.
The Touch Current of the Protective Earthing Conductor could reach up to 9mA AC.
Technical Data
Fusing and Thermal Limiting
Safety
Conformity
CE
Low Voltage [2006/95/EC] & EMC [2004/108/EC]
Directives
EN61000-6-2:2005, EN61000-6-4:2007
IEC 60335-2-80:2015 IEC 60335-1:2015
Approvals
UL61800-5-1
CSA C22.2 No113
Input Voltage Phase
Imbalance
≤2%
Input Voltage
110-240 VAC
Input Current
4.6 @ 120VAC, 2.5A @ 240VAC
Input Frequency
50-60Hz
Supported Power Systems
TT TN
For central ground systems, operation is permitted
without restrictions.
Humidity
≤ 95% Non-condensing
Temperature Range
Transport
-40°F…+160°F [40°C...+70°C]
Storage
-40°F…+160°F [40°C...+70°C]
Operation
-40°F…+120°F [40°C...+50°C] [with speed derating
above +104°F]
Installation Altitude
0-13,000 ft [0-4000 m]
above sea level
[with 5%/3000ft current derating above 3000ft]
Earth Leakage Current
<=9 mA to PE
Power Conductor Size [Cord] Minimum 16AWG 3 Conductors rated 300VAC, use Copper Conductors
only.
For permanent connection only.
Max. Permissible Control Ca-
ble Length
100 ft un-shielded
Enclosure
IP54/ NEMA 3
Protection Measures Against
Short circuit, earth fault, phase loss, over voltage, under voltage, motor
stalling, over temperature, motor overload, communication loss
Environment
For indoor use only
Thermal Overload Protection Drive provides internal overload protection for the motor
Pollution Degree
2
Overvoltage Category
Category lll
Supply Earthing System
TN-S
Impulse Voltage
2500V
Working System Voltage
150V
Packaged Fan Weight
98 lbs [44.5 kgs]
Overall Fan Weight
[no mount]
85 lbs [38.5 kgs]
LED Light Kit Weight
1.542 lbs [0.669 kgs]
Warning!
Ignoring the following instructions can cause
physical injury or death, or damage to the equipment.
Warning!
Only qualified electricians are allowed to install
the drive and connections to the motor!
General Safety
•
Installation work and electrical work must be done by qualified person[s] in accordance with all
applicable codes and standards, including fire-rated construction.
•
The installation is to be in accordance with the National Electrical Code, CSA C22.1, ANSI/NFPA
70, and local codes.
Warning!
To reduce the risk of fire, electric shock, or injury
to persons, observe the following: