ECO-X / IL-X Manual
IM100117
RD: NOV 2009
RL: 05A - BA
7
Max.
Stack
Height:
‘
H
’ = T - C
MOUNTING CLEARANCE TO COMBUSTIBLES
SUSPENDED HORIZONTALLY: Measured from outer surface of heater
MODEL
BELOW
< C >
Inches [cm]
SIDES
< S >
Inches [cm]
TOP
< A >
Inches [cm]
ENDS
< E >
Inches [cm]
ecoSchwank-X 6 - IL-X 25
ecoSchwank-X 10 - IL-X 37
ecoSchwank-X 13 - IL-X 50
ecoSchwank-X 18 - IL-X 75
ecoSchwank-X 26 - IL-X 100
60" [152]
60" [152]
78" [198]
84” [213]
84” [213]
27” [69]
27” [69]
27” [69]
33” [84]
33” [84]
24" [61]
24" [61]
24" [61]
30" [76]
36” [91]
24" [61]
24" [61]
24" [61]
30" [76]
30" [76]
FIGURE 1: MINIMUM DISTANCES TO COMBUSTIBLES - refer to
Table 1
for values
SUSPENDED AT AN ANGLE OF 30° *: Measured from outer surface of heater
NOTE: FOR AREAS USED TO STORE COMBUSTIBLE MATERIAL A ‘PEEL & STICK’ SIGN
IS SUPPLIED:
USE INDELIBLE MARKER TO RECORD VALUES ‘
H
’, ‘
S
’, ‘
F
’, & ‘
B
’.
POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A PROMINENT
LOCATION.
See next page for details.
C
S
S
SUSPENDED
HORIZONTALLY
C
A
F
B
SUSPENDED
AT 30°
TABLE 1: MINIMUM CLEARANCE TO COMBUSTIBLES
BELOW
< C >
Inches [cm]
FRONT
< F >
Inches [cm]
BACK
< B >
Inches [cm]
TOP
< A >
Inches [cm]
ENDS
< E >
Inches [cm]
60" [152]
60" [152]
78" [198]
84” [213]
84” [213]
60" [152]
60" [152]
78" [198]
84” [213]
84” [213]
24" [61]
24" [61]
24" [61]
30" [76]
30" [76]
24" [61]
24" [61]
24" [61]
30" [76]
36” [91]
24" [61]
24" [61]
24" [61]
30" [76]
30" [76]
MODEL
ecoSchwank-X 6 - IL-X 25
ecoSchwank-X 10 - IL-X 37
ecoSchwank-X 13 - IL-X 50
ecoSchwank-X 18 - IL-X 75
ecoSchwank-X 26 - IL-X 100
* NOTE
: Suspended between horizontal and 30°: Use the largest clearance from each column
~
See additional notes on previous & next pages
~
A
Site distance
to floor = T
Site distance
to floor = T
Max.
Stack
Height:
‘
H
’ = T - C