TO BE COMPLETED BY THE LICENSED INSTALLER:
HIGH INTENSITY COMMISSIONING REPORT
TYPE OF GAS:
NG
LP
DOES BUILDING HAVE A NEGATIVE CONDITION:
YES
NO
WILL HEATER BE EXPOSED TO WELDING FUMES:
YES
NO
IS HEATER EXPOSED TO CHEMICAL OR CORROSIVE ATMOSPHERE:
YES
NO
IS AN OPEN FLAME COMPATIBLE WITH THE INSTALLED LOCATION:
YES
NO
MINIMUM CLEARANCES CONFORM AS PER I&O MANUAL:
YES
NO
IF THIS IS A HIGH ALTITUDE AREA WHAT IS THE ALTITUDE ABOVE SEA LEVEL
IS HEATER SHORT AXIS HORIZONTAL WITH THE VENTURI ON TOP:
YES
NO
IS HEATER INTERLOCKED WITH AN EXHAUST FAN SYSTEM:
YES
NO
IS FAN SYSTEM 3 CFM PER 1000Btu/hr OF THE TOTAL HEAT LOAD:
YES
NO
WILL HEATER BE AFFECTED BY OVERHEAD CRANES / VIBRATION:
YES
NO
IS GAS SUPPLY LINE ADEQUATELY SIZED FOR SYSTEM VOLUME:
YES
NO
HAVE GAS LINES AND BRANCHES BEEN PURGED OF AIR:
YES
NO
THIS HEATER WAS FIELD TEST FIRED WITHOUT ANY MALFUNCTION:
YES
NO
INLET GAS SUPPLY PRESSURE WITH HEATER OPERATING:
WC"
GAS VALVE OUTLET (Manifold) PRESSURE WITH HEATER OPERATING:
WC"
HAS THE WIRING POLARITY BEEN MAINTAINED THROUGHOUT:
YES
NO
WHAT IS THE VOLTAGE READING AT THE IGNITION MODULE:
VOLTS
WHAT IS THE FLAME SIGNAL STRENGTH IN uA FROM SENSOR:
uA (microamps)
IS THE HEATER CONTROLLED BY A THERMOSTAT:
YES
NO
IS THE THERMOSTAT STRATEGICALY LOCATED:
YES
NO
TOTAL HEATERS SUPPLIED FROM ONE SINGLE TRANSFORMER:
TOTAL
WHAT IS THE RATING OF THE TRANSFORMER IN VA:
V.A.
WHAT IS THE TOTAL LENGTH OF THE LOW VOLTAGE WIRING:
FEET
WHAT IS THE GAUGE OF THE LOW VOLTAGE WIRING:
GAUGE
THIS HEATER MUST HAVE GOOD ELECTRICAL GROUNDING:
* FAX COMPLETED FORM TO TECHNICAL SERVICES: CANADA - 905-712-8336 USA - 706-554-9390
Feet
FAX COMPLETED FORM TO TECHNICAL SERVICES: 1-866-361-0523
Call Technical Services: 1-877-446-3727
LUMINOUS HEATER COMMISSIONING REPORT
IS HEATER LONG AXIS HORIZONTAL (LEVEL)
IS FAN SYSTEM CAPACITY (4 cfm /1000 Btuh USA; 300 cfm / 100,000 Btuh
Canada) CORRECT FOR THE TOTAL HEAT LOAD:
LP
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
“ WC
“ WC
NO
VOLTS
NO
NO
TOTAL HEATERS SUPPLIED BY SINGLE ZONE TRANSFORMER:
THIS HEATER MUST BE PROPERLY ELECTRICALLY GROUNDED ACCORDING TO ALL NATIONAL AND LOCAL CODES