Assembly
infraSchwank D / calorSchwank D 20U
Tools you need
• hexagonal wrench or ratchet
(width: 10, 13)
• socket wrench (width: 7 and 8)
Note before mounting
Note the distance measures of suspension brackets.
Flanges are mounted with flange packing
(each 4 screws/washers/lock washers/nuts M8).
Start mounting the heater at the turnaround box
connection.
Turn welding line of the tubes to the side.
Tube with turbulator
(with paint mark
) has to be
mounted behind the turnaround box (flow direction).
The paint mark showing to the turnaround box!
Tube bars have to be fixed by nuts/3D-washers/lock
washers M8 on the suspension brackets.
Start the reflector mounting at the turnaround box
connection with the longest reflector L=3000mm.
Reflector will be fixed on the turnaround box
connection by self-tapping screws. For insulated
reflectors (calorSchwank D) the reflector end with
notch on sides shows to the turnaround box.
The other reflector endings will be shoved under the
clips of the suspension brackets.
The short reflector L=1500mm is mounted at the
front of the heater.
Reflectors will be jointly fixed by 3x M 5 screws and
self-locking nuts.
Reflector and front plate have to be fixed by self-
tapping screws.
Mounting of burner unit with valve on the top.
Fig. 11: Mounting of infraSchwank D / calorSchwank D 20U
(all dimensions in mm)
Indirect flue into the room (Type A3):
Flue gas diverter code no. 126 70180
Note that the flue gas diverter is mounted in a
position so that the flue gas is diverted from the
burner.
Accessory:
Flue gas adapter code no. 126 7035 0
Adapter is mounted at the end of the tube with
gasket.
Flue gas connection (Type B23, C):
version stainless steel:
Note that the flue gas flexible pipe is mounted at the
end of the tube with gasket.
Flue gas diverter