GP-M40J-CX-08A
4001/2-J, 4N11/2-J Manual
RD: April 2006
R.L. 08A
KH
LEAK TEST:
For your safety you must perform a leak test of all connections and hoses.
Ensure that the connection of gas hose to burner assembly is also leak tested.
Mix equal parts of water and soap, brushing mixture on all joints.
1. Ensure that the heater gas control knob is fully closed by turning
completely clockwise.
2. Open cylinder valve for Propane or supply line for Natural Gas.
3. Apply the soap solution generously to all connections and hoses.
If you detect bubbles, there
IS
a leak. Close relevant valve completely.
Retighten the leaking connection and repeat leak test process, until
ALL
leaking has ceased, no matter how small.
If the leak cannot be repaired permanently, close the cylinder valve completely
and contact a qualified and licensed gas technician.
After successful leak test, ensure that the burner assembly and all other com-
ponents are securely fastened.
•
Lift the cylinder cover up from the base of the heater
•
Let cover rest in an angle position
•
Install a full gas cylinder on to the base
•
Connect the gas regulator to the QCC 1 cylinder valve
by turning the connector knob manually in a clockwise
direction.
•
DO NOT use a tool, hand tighten only
•
Replace the cylinder cover.
5.1 CONNECTION AND TESTING
:
•
Install sand / water filled counterweight before connecting gas supply.
•
Connect the 5” w.c. NG Gas Pressure Regulator to the flexible hose.
•
Connect the Natural Gas supply line to the flexible hose within 15ft of
the heater base.
NATURAL GAS CONNECTION 4N11/2-J & 44N1/2-J:
PROPANE CONNECTION 4001/2-J & 4401/2-J:
Page 11