Mounting Instruction
4710-5 Appliance Outlet
CONTENT
1
General
Before assembling the 4710-5 IDC-contacts with the proper wire gauge, make sure that the contacts are
clean and not twisted.
To connect the solid wires into the IDC contacts
1)
, whether the outlet is already installed in a panel or not,
the outlet should be placed on a flat surface where a force for 3 wires of up to 800 N can be applied.
Depending on the wire style (cross-section, insulation), the press-in force for one solid wire is between
150 - 250 N. Therefore, the force for three wires may reach 750 N.
1) IDC contacts according to IEC 60998-2-3,
type “r”
2
Wires for IDC-c onta ct s
4710-5
111
-XXXX-XXX-XX00
6.0 mm
2
/ 10 AWG
Insulated solid wire, single core
4710-5Y
11
-XXXX-XXX-XX00
(Y: optional type for L, see data sheet)
4710-5
222
-XXXX-XXX-XX00
4.0 mm
2
/ 12 AWG
Insulated solid wire, single core
4710-5Y
22
-XXXX-XXX-XX00
(Y: optional type for L, see data sheet)
4710-5
333
-XXXX-XXX-XX00
2.5 mm
2
Insulated solid wire, single core
4710-5Y
33
-XXXX-XXX-XX00
(Y: optional type for L, see data sheet)
Insulation
For America: According to UL 758
For Europe:
According to IEC 60228
Outer diameter shall not exceed Ø 4.5 mm
Mounting Instruction
4710-5 Appliance Outlet
CONTENT
1
General
Before assembling the 4710-5 IDC-contacts with the proper wire gauge, make sure that the contacts are
clean and not twisted.
To connect the solid wires into the IDC contacts
1)
, whether the outlet is already installed in a panel or not,
the outlet should be placed on a flat surface where a force for 3 wires of up to 800 N can be applied.
Depending on the wire style (cross-section, insulation), the press-in force for one solid wire is between
150 - 250 N. Therefore, the force for three wires may reach 750 N.
1) IDC contacts according to IEC 60998-2-3,
type “r”
2
Wires for IDC-c onta ct s
4710-5
111
-XXXX-XXX-XX00
6.0 mm
2
/ 10 AWG
Insulated solid wire, single core
4710-5Y
11
-XXXX-XXX-XX00
(Y: optional type for L, see data sheet)
4710-5
222
-XXXX-XXX-XX00
4.0 mm
2
/ 12 AWG
Insulated solid wire, single core
4710-5Y
22
-XXXX-XXX-XX00
(Y: optional type for L, see data sheet)
4710-5
333
-XXXX-XXX-XX00
2.5 mm
2
Insulated solid wire, single core
4710-5Y
33
-XXXX-XXX-XX00
(Y: optional type for L, see data sheet)
Insulation
For America: According to UL 758
For Europe:
According to IEC 60228
Outer diameter shall not exceed Ø 4.5 mm
owner
vettersa
creation date
17.08.2018
release date
17.08.2018
released by
vettersa
change order no
2016073
rev
B
page
1 of 7
D10-015-719
Product Documentation
Mounting Instruction 4710-5