Assembly and settings
8
01.00 | APS-ME1 | Assembly and Operating Manual | en | 1415570
4 Assembly and settings
4.1 Mounting and connecting the electronic processor
Ø
Mount the electronic processor in the control cabinet.
Ø
If the length of the sensor cable is not sufficient, use a cable
extension (see operating manual of the sensor).
✓
Maximum permissible cable length between sensor and
electronic processor: 10 m.
Ø
Connect the sensor or extension cable to the terminals of the
electronic processor,
Ø
Connect the shield of the sensor cable to the ground terminal.
Ø
Connect the power supply to the evaluation electronics.
Ø
Connect the multimeter or automation device to the standard
signal output (0-10 V or 4-20 mA) used.
Ø
Adjust the standard signal output to the gripper stroke,
Calibrating the electronic processor
10].
Ø
Connect the cable shield to the functional earth (FE) of the
electronic processor.
Ø
Connect shielded cable between electronic processor and
automation device,
✓
Maximum permissible cable length: 3 m.
Ø
Fine-tune the standard signal.