In order to ensure sufficient self-cleaning of the solar module, the angle of inclination should
be at least 10°. At the same time, allow for local conditions (rain quantity, formation of dust
etc.).
쮿
The solar power modules should be installed in a manner which prevents shadowing effects
(also partial shading). An ideal installation is with no shading effects at all times of year, all
day long.
쮿
Ensure that the back of the module is well vented.
쮿
Concentrating the sunlight on the module surface using mirrors or lenses is not permitted as
this can increase the temperature of the module to a dangerous state.
쮿
Only connect series solar power modules of the same type and power category.
쮿
It is not necessary to open the connector box with cables connected at the factory for
electrical switching of the solar power modules!
쮿
The solar cables are equipped with the Tyco solar-look pin-and-socket connector system for
photovoltaics.
쮿
The plugs are marked with the respective polarity (see Illustration 1). The MINUS pole is
minus-coded, the PLUS pole neutrally coded.
Illustration 1
Minus
Plus
쮿
If additional cables are needed (e.g. phase cable), only use solar cables.
쮿
Be absolutely sure to observe the solar power modules' polarity. Reverse polarity causes
destruction of the protective diodes.
Attention
Never disconnect or connect
the pin-and-socket connections under electrical load!
2. Installation tips
3. Connecting information