Instructions for Use
– SCHMIDT
®
LED Measured Value Display MD 10.010
Page 5
Mounting
Typically, the
MD 10.010
is fixed to a wall by means of four screws (pattern
of drilling see Figure 1).
Alternatively,
SCHMIDT Technology
offers a mounting kit that enables
an easy installation of the device at pipes using hose clamps (article no.
531394).
Generally, please make sure that there is enough space (approx. 11 cm)
to raise the upper part of the opened housing in order to establish electrical
connection.
Lateral compression fittings
After installation of the measured value display, the compression fittings
(included in delivery) can be mounted instead of the dummy plugs, if re-
quired.
Opening of housing
To establish electrical connection, the housing must be opened.
For this, loose the four screws of the housing completely. After that, the
screws should be pulled out as far as possible and fixed with a further left
turn in the lid so that they cannot slip back and thus block the opening of
the lid.
Inside the open housing, some components that are susceptible to ESD
are not protected against unintentional contact. Though the terminals are
resistant to ESD, the other touchable parts of the electronic system (e.g.
cover board with configuration jumper, see Figure 3) are susceptible.
Take respective protective measures to avoid damages due to
electrostatic discharge (ESD).
During electrical installation, ensure that no operating voltage is
applied and its inadvertent activation is not possible.
!