Operation Manual Flow Transmitter DW-D 

 
  

3.2  Analogue output (4-20 mA)

 

 

Connection is to block KL 1 according to the drawing.  At the connection cable a ferrite must 
be fixed. The ferrite is included in delivery. 

  

3.3  Voltage output (0-10 V)

 

 

Connection is to block KL 1 according to the drawing. (See reference point 4.3)  At the 
connection cable a ferrite must be fixed. The ferrite is included in delivery.  

  

3.4

 

Frequency output

 

 

Connection is to block KL 1 according to the drawing. (See reference point 4.3)  At the 
connection cable a ferrite must be fixed. The ferrite is included in delivery.  

 

3.5    Connecting the relais 

 

 

Relays can be connected via block KL 2 as shown on the drawing. At the connection cable a 
ferrite must be fixed. The ferrite is included in delivery. 

 

3.6    Interface

 

 

The DW-D is available to special order with RS232C interface. The special connection cable 
is just connected with the device. (See reference point 4.7) 

  

4. 

TUNING THE DW-D 

 

The device is equipped by 3 buttons on the front side of the enclosure. The button P has the 
function to choose a point of the menu and to take over the wished values. With the buttons 

 

and 

 you can set a value. Button 

 increases value. Button 

 decreases the value. Pressing 

this button one time the value changes for one digit. If you keep the buttons on hold the value 
is changing continuously. After some time velocity is increasing. At some points of the menu 
the DW-D informs you which buttons have to be pressed as next step. For example 

PIN [+/-]

,  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

3. 

ELECTRONICAL CONNECTIONS

 

 

Remove the rear access cover to gain access the 
connector blocks. 

 

(see drawing right) 

 

Block KL 2 is for connecting the relays. 

 

Block KL 1 is for connecting power supply and output 
signals. The scetch shows the relays in position of no flow 
respectivly flow is under the related switch point level. 

 

Feed the cable through the corresponding cable entry. 

 

3.1    Power Supply 

 

 

The supply-voltage is 24VDC

10%. Connection is to block 

KL 1 like described at drawing. In order to prevent the 
electronic from impermissible potential between pipe and 
device, the power supply device must be connected with 
earth. The connection is prevented from mixing the poles.  

 

At the connection cable a ferrite must be fixed with one 
coil. The ferrite is included in delivery. 

 

 

Fuse 2,5A 

+

24

V

 DC

 

0V

 DC

 

-F

req

ue

nc

y

-0

-10

V

/4

-20

m

A

 

+

F

req

ue

nc

y

-0

-10

V

/4

-20

m

A

 

 

Summary of Contents for DW-D

Page 1: ...the DW D may not directly taken close to 230V or 380V wirings The device should not be installed close to inductance switching loads engines or similar sources of inductive fields 1 3 Direction of Flow It is essential that the unit is mounted so that flow is as indicated by the arrow on the body The unit will not operate unless installed correctly in this way and the possibility of damage to the u...

Page 2: ...cket to the pipe Mount the flow transmitter to the socket ensuring that the pendulum is not damaged during this procedure Align the transmitter into the final desired position before tightening the union nut A Please do not forget to keep the flow direction in consideration before weld on the socket groove 2 4 Torsional moment of the union nut If the device shall be divided from the t piece or the...

Page 3: ...de of the enclosure The button P has the function to choose a point of the menu and to take over the wished values With the buttons and you can set a value Button increases value Button decreases the value Pressing this button one time the value changes for one digit If you keep the buttons on hold the value is changing continuously After some time velocity is increasing At some points of the menu...

Page 4: ...ting the switch point of RELAIS 1 is now completed Actuate P button once more causes changing to RELAIS 2 Adjustment is like described under RELAIS 1 When the adjusted value is reached a lamp glows for control The green one A is assigned to RELAIS 1 the red one to RELAIS 2 B 4 3 Adjusting of output occupancy DW D comes with current voltage and frequency output The different output types only can b...

Page 5: ...present at the time of power failure This guarantees that the operator is aware of that power supply was interrupted and so the amount indicated perhaps not corresponds to the real quantity Attention The power failure supervising function only works if at menu point BATT CHECK see 4 1 the function is activated ON The device has a 8 digit display so a big capacity is available Nevertheless dependin...

Page 6: ...put impermissible values will normally be transferred These are 1mA 20V respectively 0 Hz In order to re establish the function of the item in such a case the necessary software is saved additionally for safety reasons The software can be load again with the menu item FACTORY RESET Therefore push the button or in the menu FACTORY RESET You will be asked to start the action Y button or to break up ...

Page 7: ...oy the calibration Clean the pendulum system before re installing into the pipe IMPORTANT If the DW D must be separated from the tee loosen nut A and cant the unit a little opposed to direction of flow Then lift the DW D with pendulum rectangular out of the tee Please perform all disassembly reassembly operations with great care Avoid damage Especially to the pendulum system 6 TECHNICAL DATA Power...