background image

4

Operating instructions

Safety-monitoring module

SRB NA-R-C.15

EN

6.  Set-up and maintenance

6.1  Functional testing

The safety function of the safety-monitoring module must be tested. 

The following conditions must be previously checked and met:

1. Correct fixing

2. Check the integrity of the cable entry and connections

3.  Check the safety-monitoring module's enclosure for damage.

4.  Check the electrical function of the connected sensors and  

their influence on the safety-monitoring module and the  

downstream actuators

6.2  Maintenance

A regular visual inspection and functional test, including the following 

steps, is recommended:

1. Check the correct fixing of the safety-monitoring module

2. Check the cable for damages

3. Check electrical function

The device has to be integrated into the periodic check-ups 

according to the Ordinance on Industrial Safety and Health, 

however at least 1x/year.

Damaged or defective components must be replaced.

7.  Disassembly and disposal

7.1  Disassembly

The safety-monitoring module must be disassembled in a de-energised 

condition only. Push up the bottom of the enclosure and hang out 

slightly tilted forwards.

7.2  Disposal

The safety-monitoring module must be disposed of in an appropriate 

manner in accordance with the national prescriptions and legislations.

8.  Appendix

8.1  Wiring examples

One-channel control, shown for a guard door monitor with one 

positive break contact and external reset button 

J

 (see Fig. 2)

•  Relay outputs: Suitable for 2-channel control, for increase in capacity 

or number of contacts by means of contactors or relays with posi-

tive-guided contacts.

•  The control system recognises wire-breakage and earth faults in the 

monitoring circuit.

•  

S

 = Feedback circuit

K

A

K

B

L– (A2)

L+ (A1)

K1

K2

F1

C

X2

K

A

K

B

D

J

L1

N

K

A

K

B

K1

K2

13

23

14

24

33

34

41

44

X1

UB

Fig. 2

a) Logic

8.2  Start configuration

External reset button (non-monitored start) (see Fig. 3)

•  The external reset button is integrated in the feedback circuit in series.

•  The safety-monitoring module is activated upon actuation of the reset 

button.

Automatic start (Fig. 4)

•  The automatic start is programmed by connecting the feedback circuit 

to the terminals X1-X2. If the feedback circuit is not required, establish 

a bridge.

•  Caution: Not admitted without additional measure due to the risk of 

gaining access by stepping behind!

•  When the SRB NA-R-C.15 safety-monitoring module is used with 

the operating mode "Automatic start", an automatic restart after a 

shutdown in case of emergency must be prevented by the upstream 

control to EN 60204-1 paragraph 9.2.5.4.2 and 10.8.3.

X2

X1

K

A

J

K

B

X2

X1

K

A

K

B

Fig. 3

Fig. 4

Reviews: