Operating instructions

Safety-monitoring module

EN

8.3  Sensor configuration

Single-channel emergency stop circuit with command devices to 

DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 5)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Possible control categories:  

– 1 to EN 954-1  

– 2 – PL d to DIN EN ISO 13849-1

Single-channel guard door monitoring circuit with interlocking 

devices to EN 1088 (Fig. 6)

•  At least one contact with positive break required.

•  Wire breakage and earth leakage in the control circuits are detected.

•  Possible control categories:  

– 1 to EN 954-1  

– 2 – PL d to DIN EN ISO 13849-1

C

U

B

 (L+)

C

U

B

 (L+)

Fig. 5

Fig. 6

Dual-channel emergency stop circuit with command devices to 

DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 7)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are detected.

• Category 3 – PL d to DIN EN ISO 13849-1 possible.

Dual-channel guard door monitoring circuit with interlocking 

device to EN 1088 (Fig. 8)

•  At least one contact with positive break required.

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are detected.

• Category 3 – PL d to DIN EN ISO 13849-1 possible.

C

U

B

 (L+)

D

U

B

 (L–)

C

U

B

 (L+)

D

U

B

 (L–)

Fig. 7

Fig. 8

8.4  Actuator configuration

Single-channel control (see Fig. 9)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts.

•  If the feedback circuit  

is not required, establish a bridge.

•  

S

 = Feedback circuit and external reset in series

Dual-channel control with feedback circuit (Fig. 10)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts.

•  If the feedback circuit  

is not required, establish a bridge.

•  

S

 = Feedback circuit and external reset in series

X1

X2

13

14

K

A

K

A

K

A

S

L1

N

X1

X2

13

14

K

B

K

A

K

B

K

A

K

B

L1

N

K

A

S

Fig. 9

Fig. 10