6
Operating instructions
Safety-monitoring module
SRB-E-204ST / SRB-E-204PE
EN
5.3 Changing setting or application
Description / procedure
Rotary (mode) switch
System response
LED indications
RUN
In 1
In 2
Out
Factory setting
Position 1
Ready for application 1
-
-
-
-
Switch operating voltage on
Position 1
Without connected sensors!
Lights up
-
-
-
Turn to position C
Application 1 is deleted
Lights up Flashes Flashes Flashes
Setting cycle active
Application 1 is deleted
-
-
-
-
No valid application stored
Flashes
-
-
-
SRB-E ready for new applications
Select new application
Select desired application (1-11)
New application will be loaded
Lights up
-
-
-
Setting cycle active
Lights up Lights up
-
-
Lights up Lights up Lights up
-
Lights up Lights up Lights up Lights up
Ready for operation
The desired application is configured
Adopt new application
Lights up
-
-
-
Switch off operating voltage and connect wires according to selected application -> SRB-E... ready for operation