SRB 301MC

SRB 301MC-ST

Operating instructions

Safety relay module

EN

8.  Appendix

8.1  Wiring examples

Dual-channel control, shown for a guard door monitor with two 

position switches where one has a positive break contact; with 

external reset button 

J

 (Fig. 4)

•  Relay outputs: Suitable for 2-channel control, for increase in capacity 

or number of contacts by means of contactors or relays with positive-

guided contacts.

•  The control system recognises wire-breakage, earth faults and cross-

wire shorts in the monitoring circuit.

•  

S

 = Feedback circuit

K

A

K

B

K1

K2

F1

UB

Ui

A1

S12 S11 S21

K

A

K

B

L1

N

K

A

K

B

K1

K2

13

23

S22 X1

A2

14 24

33

34

41

X2

a)

nQS

QS

S

J

42

Fig. 4

a) Logic

8.2  Start configuration

External reset button (Fig. 5)

•  The external reset button is integrated in the feedback circuit in series.

•  The manual start or the activation of the module occurs when the 

button is pressed (not when it is released!).

Automatic start (see Fig. 6)

•  The automatic start is programmed by connecting the feedback circuit 

to the terminals X1-X2. If the feedback circuit is not required, establish 

a bridge.

• 

 Caution: Not admitted without additional measure due to the risk 

of gaining access by stepping behind

!

•  When the SRB 301MC safety-monitoring module is used with 

the operating mode "Automatic start", an automatic restart after a 

shutdown in case of emergency must be prevented by the upstream 

control to IEC 60204-1 paragraph 9.2.5.4.2.

Due to the operating principle of the electronic fuse, the 

customer must check that no hazard is caused by an 

unexpected restart in circuits without reset button (automatic 

reset).

X2

X1

K

A

J

K

B

X2

X1

K

A

K

B

 Fig. 5

 Fig. 6

8.3  Sensor configuration

Single-channel emergency stop circuit with command devices to 

ISO 13850 and IEC 60947-5-5 (Fig. 7)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Category 1 – PL c to ISO 13849-1 possible.

Dual-channel emergency stop circuit with command devices to 

ISO 13850 and IEC 60947-5-5 (Fig. 8)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are not detected.

•  Control category 4 – PL e to ISO 13849-1 possible (with protective 

wiring)

Dual-channel emergency stop circuit with command devices to 

ISO 13850 and IEC 60947-5-5 (Fig. 9)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are detected.

•  Category 4 – PL e to ISO 13849-1 possible.

S12

S11

S22

S12

nQS
QS

S12

S11

S22

S21

nQS
QS

S12

S11

S22

S21

nQS
QS

Fig. 7

Fig. 8

Fig. 9

Single-channel guard door monitoring circuit with interlocking 

devices to ISO 14119 (Fig. 10)

•  At least one contact with positive break required.

•  Wire breakage and earth leakage in the control circuits are detected.

•  Category 1 – PL c to ISO 13849-1 possible.

Dual-channel guard door monitoring circuit with interlocking 

device to ISO 14119 (see Fig. 11)

•  At least one contact with positive break required.

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the monitoring circuits are not detected.

•  Control category 4 – PL e to ISO 13849-1 possible (with protective 

wiring)

Dual-channel guard door monitoring circuit with interlocking 

device to ISO 14119 (see Fig. 12)

•  At least one contact with positive break required.

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the guard monitoring circuits are detected.

•  Category 4 – PL e to ISO 13849-1 possible.

S12

S11

S22

S12

nQS
QS

S12

S11

S22

S21

nQS
QS

S12

S11

S22

S21

nQS
QS

Fig. 10

Fig. 11

Fig. 12

Summary of Contents for SRB 301MC

Page 1: ...odule must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found...

Page 2: ...061 To determine the Performance Level PL to ISO 13849 1 1 of the entire safety function e g sensor logic actuator an assessment of all relevant components is required The entire concept of the contro...

Page 3: ...e enclosure slightly tilted forwards in the standard rail and push up until it latches in position To avoid EMC disturbances the physical ambient and operational conditions at the place where the prod...

Page 4: ...S12 14 24 34 S21 42 X2 A2 S22 41 X1 A1 S12 18 28 38 S22 45 X1 A1 nQS QS Fig 1 Fig 2 Fig 3 6 Set up and maintenance 6 1 Functional testing The safety function of the safety monitoring module must be te...

Page 5: ...l emergency stop circuit with command devices to ISO 13850 and IEC 60947 5 5 Fig 7 Wire breakage and earth leakage in the control circuits are detected Category 1 PL c to ISO 13849 1 possible Dual cha...

Page 6: ...toring module is only admitted when the requirements of the standard IEC 60947 5 3 are observed As the technical data are regarded the following minimum requirements must be met switching capacity min...

Page 7: ...ype test T V Rheinland Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5035 01 16 Person authorised for the compilation of the technical documentation O...

Page 8: ...K A Schmersal GmbH Co KG M ddinghofe 30 42279 Wuppertal Germany Phone 49 202 6474 0 Telefax 49 202 6474 100 E Mail info schmersal com Internet www schmersal com...

Reviews: