Operating instructions

Safety sensor

EX-BNS 33

EN

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

EX-BNS 33-

Z

-3G/D

No.

Option

Description

11

1 NO contacts / 1 NC contacts

12

1 NO contact / 2 NC contact

without LED

G

with LED

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond  

to the standard version.

2.3  Purpose

The safety sensor can be used for monitoring the position of movable 

guards and flaps in explosion-endangered areas of Zone 2 and 22 

category 3GD. Installation and maintenance requirements to the 

standard series EN 60079 must be met. For the actuation of the safety 

sensors, only the EX-BPS 33 actuator can be used. 

The safety switches are used for applications, in which the hazardous 

situation is terminated without delay when the safety guard is opened.

The safety switchgears are classified according to  

ISO 14119 as type 4 interlocking devices.

Only the entire system consisting of the safety sensor (EX-BNS), the 

actuator (EX-BPS) and the safety-monitoring module (AES/SRB/AZR) 

meet the requirements of the standard IEC 60947-5-3.

Conditions for safe operation

Due to their specific impact energy, the components must be fitted 

with a protection against mechanical stresses. The specific ambient 

temperature range must be observed. The user must provide for a 

protection against the permanent influence of UV rays. The energy 

restriction for LED versions (24 V/10 mA) must be ensured by the user.

The user must evaluate and design the safety chain in 

accordance with the relevant standards and the required 

safety level.

The entire concept of the control system, in which the safety 

component is integrated, must be validated to the relevant 

standards. 

2.4  Technical data

Equipment category:

 

L

 II 3GD

Ex protection:

 

 

- EX-BNS 33: 

 

Ex nC IIC T6 Gc X; 

Ex tc IIIC T80°C Dc X 

- EX-BPS 33: 

 

Ex h IIC T6 Gc;  

Ex h IIIC T80°C Dc 

Standards:

 

IEC 60947-5-3, EN 60079-0, EN 60079-15,  

EN 60079-31, EN 13463-1, ISO 80079-36, ISO 80079-37,  

BG-GS-ET-14

Design:

 rectangular

Enclosure:

 

glass-fibre reinforced thermoplastic

Max. impact energy:

 

1 J

Protection class: 

IP67 to IEC 60529

Connection:

 

Boflex cable

Cable section:

 

4 x 0.25 mm²

Operating principle:

 magnetic

Actuating magnet:

 

EX-BPS-33, coded

Coding level according to ISO 14119:

 low

assured switching distance s

ao

:

 

5 mm

assured switch-off distance s

ar

:

 

15 mm

Switching condition indication:

 

LED only with ordering suffix G

Switching voltage max.:

 

without LED: 100 VAC / DC 

with LED: 24 VDC

Switching current max.:

 

without LED: 400 mA 

with LED: 10 mA

Switching capacity max.:

 

without LED: 10 W 

with LED: 240 mW

Ambient temperature: 

 

−25 °C ... +70 °C

Storage and transport temperature:

 

−25 °C ... +70 °C

Repeat accuracy R:

 

≤ 0.1 x s

ao

Max. switching frequency:

 

ca. 5 Hz

Resistance to shock:

 

30 g / 11 ms

Resistance to vibration:

 

10 ... 55 Hz, amplitude 1 mm

2.5  Safety classification

Standards: 

ISO 13849-1

B

10D

 (NC/NO contact): 

25.000.000  

at max. 20 % contact load

Service life: 

20 years

MTTF

B

d x

x

h

s/h

3600

D

10D

op

op

op

n

0,1 x n

op

t

cycle

(Determined values can vary depending on the application-specific 

parameters h

op

, d

op

 and t

cycle

 as well as the load.)

An individual switch can be used in a category 3 or 4 architecture up to 

PL e.

If multiple safety components are wired in series, the Performance 

Level to ISO 13849-1 will be reduced due to the restricted error 

detection under certain circumstances.

Summary of Contents for EX-BNS 33

Page 1: ...ons listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations and accident preve...

Page 2: ...tion against mechanical stresses The specific ambient temperature range must be observed The user must provide for a protection against the permanent influence of UV rays The energy restriction for LED versions 24 V 10 mA must be ensured by the user The user must evaluate and design the safety chain in accordance with the relevant standards and the required safety level The entire concept of the c...

Page 3: ...uld always be at least 50 mm Please observe the specifications for the maximum impact energy in the technical data Safety sensor and actuator must be permanently fitted to the safety guards and protected against displacement by suitable measures tamperproof screws gluing drilling of the screw heads 3 2 Dimensions All measurements in mm Safety sensor with cable 88 78 25 7 3 5 18 5 7 5 6 5 1000 4 5 ...

Page 4: ... input expander module As a result of this the luminosity of the LED s would considerably decrease and the voltage could drop below the minimum input voltage of the downstream safety monitoring module In case of series wiring at SRB max 1 sensor with LED indication for UN Inductive loads e g contactors relays etc are to be suppressed by means of a suitable circuit If the EX BNS 33 with LED is used...

Page 5: ... EU 2011 65 EU Applied standards DIN EN 60947 5 3 2014 EN 60079 0 2012 A11 2013 EN 60079 15 2010 EN 60079 31 2014 EN ISO 80079 36 2016 EN ISO 80079 37 2016 Notified body which approved the full quality assurance system referred to in Appendix IV 2014 34 EU TÜV Rheinland Industrie Service GmbH Am Grauen Stein 51105 Köln ID n 0035 Person authorised for the compilation of the technical documentation ...

Page 6: ... A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...

Reviews: