Operating instructions

Emergency stop command device

EN

Tightening torque for the connecting screw: 

max. 1 Nm

Cable sections:

 

 

- single-strand:

 

2 x (0.5 … 2.5 mm²) 

- multi-strand:

 

2 x (0.5 … 1.5 mm²) 

- Flat plug-in connector:

 

6.3 mm x 0.8 mm / 2 x 2.8mm x 0.8 mm 

Protection class: 

 

- Terminals: 

IP20 (finger guard) 

- Wiring compartments: 

 IP40 

 

(with plug-in connector depending on the connector plug used)

Approvals: 

 

cULus (save cage clamp connection)

2.5  Safety classification

Standards: 

ISO 13849-1

B

10D

 (NC contact):

 100,000

Service life: 

20 years

MTTF

B

d x

x

h

s/h

3600

D

10D

op

op

op

n

0,1 x n

op

t

cycle

3.  Mounting

3.1  General mounting instructions

1.  Fit the EDRRS… emergency stop actuator in non-actuated  

condition by means of the ELM mounting flange, align and tighten 

(max. 0.6 Nm).

2.  Snap the EFR.EDRRS or EFR spring elements in the middle  

position of the ELM mounting flange (position 3).

3.  The EMERGENCY STOP actuator EDRRS... is latched, (i.e. 

mechanically fixed), to the EFR.EDRRS or EFR spring element by 

actuation. By releasing with the key and pulling on the EMERGENCY 

STOP actuator, the spring element is tensioned again and the 

EMERGENCY STOP is returned to the ready position. 

4.  Snap the desired EF... contact elements onto the free positions to 

the right and to the left (position 1 and 2) next to the EFR.EDRRS or 

EFR spring element.

5.  Mounting of the securing plate:

EFR.EDRRS with earth connection

a)

b)

c)

d)

f)

e)

a ) EFR.EDRRS (Spring element with earth connection)

In the EFR.EDRRS kit:

b ) Securing plate

c ) Securing ring

d ) 2x serrated lock washer

e ) Nut

f ) Earth connection

Tightening torque of the nuts max. 0.6 Nm. Required tool: 

screwdriver, spanner with width across flats 8.

EFR without earth connection

a)

b)

c)

c)

a ) EFR (Spring element without earth connection)

In the EFR kit:

b ) Securing plate

c ) 2x securing ring

3.2  Dimensions

3.3  Emergency stop command device EDRRS…

Ø 39

29

i)

g)

h)

f)

e)

d)

c)          

b)

a)

a) Key

b) EDRRS emergency stop actuator

c) Emergency stop label

d) Enclosure or mounting panel

e) Clamping element

f) Mounting flange ELM

g) Contact element EF

h) EFR.EDRRS or EFR

i) EFR.EDRRS or EFR kit

Contact elements of the EF contact system must be fitted in 

the second locking position and must, therefore, lie flush on 

the mounting flange after fitting.