3
EDRRS40...
Operating instructions
Emergency stop command device
EN
Tightening torque for the connecting screw:
max. 1 Nm
Cable sections:
- single-strand:
2 x (0.5 … 2.5 mm²)
- multi-strand:
2 x (0.5 … 1.5 mm²)
- Flat plug-in connector:
6.3 mm x 0.8 mm / 2 x 2.8mm x 0.8 mm
Protection class:
- Terminals:
IP20 (finger guard)
- Wiring compartments:
IP40
(with plug-in connector depending on the connector plug used)
Approvals:
cULus (save cage clamp connection)
2.5 Safety classification
Standards:
ISO 13849-1
B
10D
(NC contact):
100,000
Service life:
20 years
MTTF
B
d x
x
h
s/h
3600
D
10D
op
op
op
n
0,1 x n
op
t
cycle
3. Mounting
3.1 General mounting instructions
1. Fit the EDRRS… emergency stop actuator in non-actuated
condition by means of the ELM mounting flange, align and tighten
(max. 0.6 Nm).
2. Snap the EFR.EDRRS or EFR spring elements in the middle
position of the ELM mounting flange (position 3).
3. The EMERGENCY STOP actuator EDRRS... is latched, (i.e.
mechanically fixed), to the EFR.EDRRS or EFR spring element by
actuation. By releasing with the key and pulling on the EMERGENCY
STOP actuator, the spring element is tensioned again and the
EMERGENCY STOP is returned to the ready position.
4. Snap the desired EF... contact elements onto the free positions to
the right and to the left (position 1 and 2) next to the EFR.EDRRS or
EFR spring element.
5. Mounting of the securing plate:
EFR.EDRRS with earth connection
a)
b)
c)
d)
f)
e)
a ) EFR.EDRRS (Spring element with earth connection)
In the EFR.EDRRS kit:
b ) Securing plate
c ) Securing ring
d ) 2x serrated lock washer
e ) Nut
f ) Earth connection
Tightening torque of the nuts max. 0.6 Nm. Required tool:
screwdriver, spanner with width across flats 8.
EFR without earth connection
a)
b)
c)
c)
a ) EFR (Spring element without earth connection)
In the EFR kit:
b ) Securing plate
c ) 2x securing ring
3.2 Dimensions
3.3 Emergency stop command device EDRRS…
Ø 39
29
i)
g)
h)
f)
e)
d)
c)
b)
a)
a) Key
b) EDRRS emergency stop actuator
c) Emergency stop label
d) Enclosure or mounting panel
e) Clamping element
f) Mounting flange ELM
g) Contact element EF
h) EFR.EDRRS or EFR
i) EFR.EDRRS or EFR kit
Contact elements of the EF contact system must be fitted in
the second locking position and must, therefore, lie flush on
the mounting flange after fitting.