CSS 8-180

Operating instructions

Safety sensor

EN

Safety inputs X1/X2: 

Rated operating voltage U

e

:

 

24 VDC -15% / +10% 

 

PELV (to IEC 60204-1)

Rated operating current I

e

1 A

Accepted test pulse duration on input signal:

 

≤ 1.0 ms

 

- With test pulse interval of:

 

≥ 100 ms

Classification:

 

ZVEI CB24I  

Sink:

C1

Source:

C1

C2

C3

Safety outputs Y1/Y2: 

p-type, short-circuit proof

Rated operating current I

e1

:

 

max. 0,5 A  

depending on the ambient temperature

Utilisation category:

 

DC-12 U

e

/I

e

 24 VDC / 0.5 A 

DC-13 U

e

/I

e

 24 VDC / 0.5 A

Voltage drop:

 

0.5 V

Leakage current l

r

:

 

< 0.5 mA

Test pulse duration:

 

≤ 2.0 ms

Test pulse interval:

 

2,000 ms

Classification:

 

ZVEI CB24I  

Source:

C0

Sink:

Diagnostic output:

 

short-circuit proof, p-type

Rated operating voltage U

e2

:

 

max. 4 V below U

e

Operating current I

e2

:

 

max. 0.05 A

Utilisation category:

 

DC-12 U

e

/I

e

 24 VDC / 0.05 A 

DC-13 U

e

/I

e

 24 VDC / 0.05 A

External fuse rating:

 fuse: 

 

1.0 A at output current  ≤ 200 mA

 

 

1.6 A at output current  > 200 mA

2.6  Classification

Standards:

 

ISO 13849-1, IEC 61508

PL:

 e

Control Category:

 4

PFH:

 

2.5 x 10

-9

 / h

SIL:

 

suitable for SIL 3 applications

Mission time: 

20 years

3.  Mounting

3.1  General mounting instructions

During fitting of the actuator and the sensor, the requirements 

of ISO 14119, especially paragraph 7 must be observed.

The component can be mounted in any position. The only condition 

is that, the active surface of the safety sensor and the actuator are 

opposite. The sensor enclosure must not be used as an end stop. The 

safety sensor must only be used within the assured switching distances 

≤ s

ao

 and ≥ s

ar

.

The safety sensor and the corresponding actuator can be fixed 

using the supplied M18 nuts (A/F 24). The max. tightening torque of 

the supplied screws is 500 Ncm. Alternatively, the H18 fixing clamp 

(accessory) can be used for the fixation of the safety sensor.

A concealed mounting is possible, however this reduces the switching 

distance. The reduction will be lower, when the safety sensor protrudes 

a few mm.

The CST 180-1 actuator has two fixing holes displaced by 90°. The 

max. tightening torque of the supplied screws is 100 Ncm.

The CST-180-2 actuator is screwed into a prepared tapped hole M 18. 

Use the slot to the front.

The actuator and/or clamp must be permanently fitted to the 

guard system and protected against displacement by suitable 

measures (tamperproof screws, gluing, drilling of the screw 

heads, pinning).

To avoid any interference inherent to this kind of system and any 

reduction of the switching distances, please observe the following 

guidelines:

• The presence of metal chips in the vicinity of the sensor is liable to 

modify the switching distance

• Keep away from metal chips

• Minimum distance between two sensors: 100 mm

When used at ambient temperatures < -10 °C, the connecting 

cables must be hardwired.

Summary of Contents for CSS 8-180

Page 1: ...ised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention rules Further technical information can b...

Page 2: ...tion the safety sensor monitors the position of hinged sliding or removable safety guards by means of the coded electronic CST 180 1 or CST 180 2 actuators Mode of operation of the safety outputs The opening of a safety guard i e the actuator is removed out of the active zone of the safety sensor will immediately disable the safety outputs also refer to Switching distance of the safety sensor Seri...

Page 3: ...unted in any position The only condition is that the active surface of the safety sensor and the actuator are opposite The sensor enclosure must not be used as an end stop The safety sensor must only be used within the assured switching distances sao and sar The safety sensor and the corresponding actuator can be fixed using the supplied M18 nuts A F 24 The max tightening torque of the supplied sc...

Page 4: ...ly lit yellow In this position a reliable switching position of the sensor is obtained also refer to Operating Principle of the Diagnostic Outputs The proper functionality must always be checked by means of the connected safety monitoring module 3 4 Switch distance The graphs show the switch on and switch off points of the sensor due to the approach of the actuator The maximum misalignment of the ...

Page 5: ...necting cables must be taken as large as possible Wiring examples for series wiring refer to appendix 4 3 Note on the total length of a safety sensor chain The voltage drop of a long sensor chain must be taken into account when planning the wiring Typical resistance of the different sensor connecting cables 20 C 0 50 mm2 approx 36 Ω km 0 34 mm2 approx 52 Ω km 0 25 mm2 approx 71 Ω km The resistance...

Page 6: ... a safety related output The diagnostic output can also be used to detect clearance variations between the sensor and the actuator in the same way as the yellow LED An active fault causes the diagnostic output to be disabled The safety outputs are disabled after max 30 minutes if the fault is not rectified The signal combination diagnostic output disabled and safety channels still enabled can be u...

Page 7: ...nsor and so on A 200m long sensor chain can be set up A safety sensor of the CSS 8 180 2P Y L type can also be used as a terminal device in a chain in this situation additional wiring is required The positive operating voltage must be wired to both safety inputs Wiring example 2 Safety monitoring module 24V 0V GY BN BU WH VT BK WH 0V WH VT 0V GY BK RD 0V WH VT 0V BN BU BN BU BN BU GY BK RD GY BK R...

Page 8: ... cable with connector Inputs IN female connector M12 4 pole 0 25 m Outputs OUT male connector M12 4 pole 2 m 3 2 5 1 4 3 2 5 1 4 Female connector IN Male connector OUT Lead colours connecting cable Wiring grey cable IN Black cable OUT Pin configuration of the connector BN brown A1 Ue A1 Ue Pin 1 BU blue A2 GND A2 GND Pin 3 BK black X1 safety input 1 Y1 safety output 1 Pin 4 WH white X2 safety inpu...

Page 9: ...X1 Safety input 1 2 BN WH WH A2 GND 3 GN BU BU Y1 Safety output 1 4 YE BK BK OUT Diagnostic output 5 GY GY GY X2 Safety input 2 6 PK VT PK Y2 Safety output 2 7 BU RD VT IN without function 8 RD PK OR Colour code key Code Colour Code Colour Code Colour Code Colour BK black GN green PK pink WH white BN brown GY grey RD red YE yellow BU blue OR orange VT violet Connecting cables with coupling female ...

Page 10: ...est certificate IFA 1001232 Person authorised for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal February 3 2017 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH Co KG Möddinghofe 30 42279 Wuppertal Germany Internet www schmersal com We hereby certify that ...

Reviews: