2

Operating instructions

Solenoid interlock

AZM 415-22

AZM 415-33

EN

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories. 

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

AZM 415-22ZPK

-M20 24 VAC/DC

No. Option

Description

Power to unlock

A

Power to lock

AZM 415-33ZPDK

➀➁

 

➂➃

 

No. Option

Description

Power to unlock

A

Power to lock

ST

M23 connector at the right-hand side

STL

M23 connector at the left-hand side

without manual release

E

Manual release using triangular key  

(only for power to unlock principle)

1637

gold-plated contacts

24 VAC / DC

U

s

 24 VAC

110 VAC

U

110 VAC

230 VAC

U

s

 230 VAC

Only if the information described in this operating instructions 

manual are realised correctly, the safety function and 

therefore the compliance with the Machinery Directive is 

maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Purpose

The AZM 415 solenoid interlock has been designed to prevent movable 

safety guards, e.g. fences, covers or doors, in conjunction with the 

control part of a machine, e.g. fail-safe delay timers or fail-safe standstill 

monitors, from being opened before hazardous conditions (e.g. run-on 

mouvements) have been eliminated. The AZM 415-33 includes three 

switch inserts and is designed for monitoring double safety guards.

Interlocks with power to lock principle may only be used in 

special cases after a thorough evaluation of the accident risk, 

since the safety guard can be opened immediately on failure 

of the power supply or upon activation of the main switch. 

The safety switchgears are classified according to 

ISO 14119 as type 2 interlocking devices.

Solenoid interlock with manual release AZM 415-33PDKE

The manual release is only used with components that operate on the 

power to unlock principle. It is used as a mounting tool and also as a 

tool to open a closed and locked safety guard in case of a power failure. 

The point of access to the manual release or the manual release itself 

must be protected in accordance with the provisions of the professional 

association, e.g. by sealing during mounting.

Unlocking: 

using triangular key (available as accessory)

Reset: 

by turning the triangular key back

The user must evaluate and design the safety chain in 

accordance with the relevant standards and the required 

safety level.

The entire concept of the control system, in which the safety 

component is integrated, must be validated to the relevant 

standards.

2.4  Technical data

Standards:

 

IEC 60947-5-1, ISO 14119

Enclosure:

 

light-alloy die-cast, enamel finish

Actuator and locking bolt:

 

zinc-plated metal / aluminium

Locking force F: 

 

- AZM 415-22:

 

3,500 N 

- AZM 415-33:

 

2,500 N (each safety guard)

Latching force:

 

150 ... 400 N (adjustable)

Coding level according to ISO 14119: 

 low

Ambient temperature:

 

−25 °C … + 50 °C

Protection class:

 IP67

Degree of pollution:

 3

Positive break travel (unlocked):

 

AZM 415-22: 5 mm 

AZM 415-33: 4,5 mm

Positive break force (unlocked):

 

min. 15 N (depending on  

the setting of the ball latch)

Actuating speed:  

max. 0.2 m/s

Max. actuating frequency:

 

2,000 s/h

Mechanical life:

 

> 1,000,000 operations

Contact material:

 Silver

Contact types:

  

Change-over contact with double break, type Zb  

or 2 NC contacts, with galvanically  

separated contact bridges

Switching system:

 

A

  IEC 60947-5-1; slow action, NC contact with 

positive break

Connection:

 

screw terminals

Cable type:

 

rigid / flexible

Cable section:

 

min. 0.75 mm² - max. 2.5 mm² 

(including conductor ferrules)

Cable entry:

 

2 x M20 x 1.5

Electrical data:

Utilisation category:

 AC-15

Rated operating current/voltage I

e

/U

e

:

 

4 A / 230 VAC

Rated impulse withstand voltage U

imp

:

 

4 kV

Rated insulation voltage U

i

:

 

250 V

Thermal test current I

the

:

 

6 A

Max. fuse rating:

 

6 A gG D-fuse

Required rated short-circuit current:

 

1,000 A

Magnet switch-on time:

 

100 %

Rated control voltage U

s

:

 

24 VAC / DC, 

110 VAC, 50 / 60 Hz, 

230 VAC, 50 / 60 Hz,

Power consumption:

 

max. 10 W