background image

7

AST LC ST-AS

Operating instructions

Opto-Tube

EN

4. Rear side Electrical connection

4.1  General information for electrical connection

The electrical connection to the AS-i system may only be 

carried out by authorised personnel in a de-energised 

condition (refer to EN 50295).

Connection to the AS-Interface system

The connection to the AS-Interface system is realised through an M12 

connector (ST). The following wiring configuration is applicable for the 

AS-i Slave (cable configuration to EN 50295):

ST

1:

AS-i +

3

2

1

4

2:

spare

3:

AS-i -

4:

spare

Connection of the light grid (receiver)

The connection to the light grid (E) is realised through an M12 

connector (ST2). The wiring configuration is as follows:

ST2

1:

+ 24 VDC

3

2

5

1

4

2:

OSSD 1

3:

GND

4:

OSSD 2

5:

FE (functional earth connection)

Connection of the 24V voltage supply of the light grid

The 24V voltage supply (PELV unit to IEC 364-4-41) is connected 

through an M12 connector (ST1). The wiring configuration is as follows:

ST1

1:

+ 24 VDC

3

2

5

1

4

2:

spare

3:

GND

4:

spare

5:

FE (functional earth connection)

For the installation of the Opto-Tube and a light grid, the following 

boundary conditions must be observed:

 -  the voltage supply of the light grid (E) is connected through the

looped-through connecting cable from the control cabinet

-  the protective wire connection for the light grid is looped through as well

-  the connecting cable between the Opto-Tube and the light grid must

be 5 m at the most

-  the emitter of the light grid (refer to light grid description) must have a

separate voltage supply

5. Configuration

5.1  Programming the slave address

The slave address is programmed through the M12 connector (ST).  

Any address from 1 to 31 can be set by means of the AS-i bus master 

or a hand-held programming device.

5.2  Configuration of the safety monitor

The Opto-Tube can be configured application-dependent in the ASM 

safety monitor. To this effect, two monitoring devices are recommended: 

double channel with positive break and double channel dependent.  

If the double channel dependent monitoring device with synchronisation 

time ∞ (endless) is used, the start-up test must be activated. 

 

An automatic start is not authorised without additional start condition.

The configuration of the safety monitor must be tested and 

confirmed by a qualified and authorised safety expert/safety 

engineer.

5.3  Status signal "safety release"

The "safety release" status signal from a Safety at Work slave can be 

cyclically queried by the control system through the AS-i master.  To 

that effect, the 4 input bits with the varying SaW code of a Safety at 

Work slave are evaluated through an OR operation with 4 inputs in the 

control system.

In order to ensure a correct function of the Opto-Tube, the 

parameter port must be set to the default value F hex (1111) 

according to the AS-i specification.

Safety instructions

In case for an interruption of the 0 volt cable for the 

connected light grid or light curtain, the max. output current 

(leakage current) of the OSSD (refer to technical data of 

the non-contact safety switchgear) must not exceed 0.5 

mA. The Opto-Tube has a response time of ≤ 20 ms during 

the safety switch-off procedure. To calculate the minimum 

safety distance of the non-contact safety switchgear, the 

total response time, consisting of the response time of the 

non-contact safety switchgear, the Opto-Tube, the AS-i safety 

monitor and the machine standstill time must be observed.

6. Set-up and maintenance

6.1  Functional testing

The safety function of the Opto-Tube AST LC ST-AS must be tested. 

The following conditions must be previously checked and met:

1. Check for damages

2. Check the integrity of the cables and connections

6.2  Maintenance

A regular visual inspection and functional test, including the following 

steps, is recommended:

1. Check for damages

2. Remove particles of dust and soiling

3. Check the integrity of the cables and connections

Damaged or defective components must be replaced.

7. Disassembly and disposal

7.1  Disassembly

The safety switchgear must be disassembled in a de-energised 

condition only.

7.2  Disposal

The safety switchgear must be disposed of in an appropriate manner in 

accordance with the national prescriptions and legislations.

mrl_opto-tube_en.indd   7

23.11.2017   16:10:14

Summary of Contents for AST LC ST-AS

Page 1: ...hr nderungen die dem technischen Fortschritt dienen vorbehalten Werden mehrere Sicherheitskomponenten in Reihe ge schaltet wird der Performance Level nach EN ISO 13849 1 aufgrund verringerter Fehlere...

Page 2: ...ionen freigegeben Die Bewertung und Auslegung der Sicherheitskette ist vom Anwender entsprechend der relevanten Normen und Vor schriften und in Abh ngigkeit vom erforderlichen Sicherheits niveau vorzu...

Page 3: ...der Verwendung des berwachungsbaustei nes zweikanalig abh ngig mit Synchronisationszeit unendlich muss zus tzlich der Anlauftest aktiviert werden Der Automatische Start ist ohne zus tzliche Startbedi...

Page 4: ...08 Teile 1 7 2010 Bevollm chtigter f r die Zusammen stellung der technischen Unterlagen Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach...

Page 5: ...in the online catalogue on the Internet www schmersal net The information contained in this operating instructions manual is provided without liability and is subject to technical modifications If mul...

Page 6: ...nd design the safety chain in accordance with the relevant standards and the required safety level LED display The LED s have the following meaning to EN 50295 Green LED AS Interface supply voltage Re...

Page 7: ...ependent monitoring device with synchronisation time endless is used the start up test must be activated An automatic start is not authorised without additional start condition The configuration of th...

Page 8: ...13849 1 2016 IEC 61508 parts 1 7 2010 Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279...

Reviews: