Operation Instructions
34 / 42
EN-US · 30.30.01.02533 · 00 · 11/20
5. Press
or
button to setting OUT 2.
OUT2 OFF = [
off
]
OUT2 ON = [
on
]
6. Press
button to return to "Function Selec-
tion Mode".
6.16 Reset to the Default Setting
[
F-99
] The factory default settings can be restored.
1. Press
or
button at "Function Selec-
tion Mode" to display [
F-99
] [
re5t
].
2. Press
button to switch to "Reset to The De-
fault Setting".
3. Press
or
button to return to the fac-
tory default setting.
Disable = [
off
]
Enable = [
on
]
4. Press
button to return to "Function Selec-
tion Mode".
6.17 Pressure Zero Adjustment Function
The displayed value can be adjusted to "0" when the pressure is within ±3% of the zero point at the time
of shipment from the factory.
ü
Sensor is at measurement mode.
1. Press
and
simultaneously over 3 sec. until display [
00
].
2. Release holding the buttons to return measurement mode.
ð
Pressure value return zero.
6.18 Instantaneous Flow Zero Adjustment Function
The displayed value can be adjusted to "0" when the measured flow is within ±10% F.S. of the zero point
at the time of shipment from the factory.
ü
Sensor is at measurement mode.
1. Press
and
simultaneously over 3 sec. until display [
00
].
2. Release holding the buttons to return measurement mode.
ð
Instantaneous flow value return zero.