Installation and commissioning DATAEAGLE 4XXX Compact
6-1
Chapter 6
– Filter time
6.
Increasing the system availability
(Profinet only)
6.1. Function
The
filter time
is used to suppress short radio interferences.
This function is only active for cyclical data transmission like
Profinet.
If a radio slave cannot be accessed due to an interference, a
bus error is indicated to the Profinet controller only after the
filter time has been elapsed. Only then are the outputs of the
connected Profinet devices switched into safe condition.
The advantage is that Profinet bus errors can be supressed
for an adjustable time and thus the system availability van ib
increased.
6.2. Setting of the filter time at Radio Master
and Radio Slave
Connect the
Radio Master/Slave
with the USB cable to
the PC.