Installation and commissioning DATAEAGLE 3XXX Classic
Chapter 7
– Diagnostic slave
Block 0: General diagnostic values
Position
Meaning
Value
Control Value
Byte 0
Baud rate
1 : 1,5 MBd
2: 500 kBd
3. 187,5 kBd
4: 93,75 kBd
5: 19,2 kBd
6: 9,6 kBd
Display number (here: 0)
Byte 1
Filter setting [100ms]
1
– 255 (100ms – 25,5s)
0: no function
1: reset counter
Byte 2
Power-Up counter
Counts the transients of the
DATAEAGLE master
Byte 3
Quantity of Profibus
errors
Byte 4 / 5
Sum of retries of the
radio interface
Counts the telegrams which
could not be responded from
the slaves
Byte 6 / 7
Quantity of slave
failures
Sum of all interrupted
connections from the
transmitter side ->
DATAEAGLE master reports
bus error
Byte 8 / 9
Sum of all slave
responding telegrams
Byte 10
–13 DATAEAGLE device
type
ASCII coded, e.g. „3002“
Byte 14
– 17 DATAEAGLE Software
version
ASCII coded, e.g. „9.75“
Byte 18
–21 Software Profibus
interface
ASCII coded, e.g. V 42“
Byte 22 Radio channel
Set radio channel, depending
on type
Byte 23 HF Retries
Set HF Retries
Byte 24 HF Power
Transmitter power,
depending on type
Byte 25 Radio device address
Byte 26 Radio partner address
Byte 27 Operation mode
Master / Slave
Byte 28 Relay timeout
Set relay time of the radio
monitoring
Byte 29-30
Byte 31 0
Feedback from display side
(here 0)