Installation and commissioning DATAEAGLE 3XXX Classic
Check radio
modules
Chapter 5
– Extension and exchange
Check the firmware version at all radio modules in the
system.
Profibus-Slave-Addresses are automatically detected from
firmware version DE32_M83 or DE32_S83.
If one of the radio modules in the system has an older
firmware version (e.g. DE32_M82 or lower) you
must
assign
Profibus-Slave-Addresses in the new Radio Master.
If all radio modules in the system have a newer firmware
version (e.g. DE32_M83 or higher) you
must not
assign
Profibus-Slave-Addresses in the new Radio Master. They are
detected automatically.
Continue with de-installation of the Radio Master (chapter
5.3.1)
Firmware
version