Schebler eVent Installation Instructions, Operation And Maintenance Manual Download Page 11

11 

 

FLASHING and RAIN COLLAR (FL and RC) 

 

Both the Flashing and the Rain Collar are designed to fit the 
outside of the Model eVent Series Venting System.  They are 
constructed of galvanized steel and should be protected 
from corrosion by cleaning and painting.  The Flashing is 
non‐ventilated and for non‐combustible and combustible 
flat roofs.  Flashings of a special pitch are available upon 
request.  The Flashing should be protected from lateral 
movement of the stack by use of the Full Ring (FR) or the 
Floor/Roof Guide (FRG). The Rain Collar is secured around 
the pipe immediately above the flashing and should be 
sealed with a silicone sealant. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Figure 31 –Roof Penetrations 

 

If the height above the roof line is less than that specified on 
page 13, no guying or bracing is required. However, an 
Insulated Thimble (IT), Floor/Roof Guide (FRG) or Full Ring 
(FR) at the roof line is necessary to protect the Flashing (FL) 
from side loads caused by wind. For heights above the roof 
line greater than that shown on page 13, the vent must be 
guyed or braced.  Guying or bracing is accomplished by use 
of the Guy Section (GS) Full Ring (FR) or Wall Guide (WG).  
Guy wires or braces are to be attached to the horizontal 
flanges of the Guy Section. While 3 guys are usually 
sufficient, it is recommended that 4 equally spaced wires at 
an angle of 45° from the vertical be utilized. The cables and 
guys must be slightly loose to allow for the thermal 
expansion.  Rigid bracing requires two braces with not less 
than 60° angle between them.  The braces must be attached 
to a Guy Section (GS) or Full Ring (FR). 

 
See page 12 for further instructions. 
 
 
 
 
 
 

TOP SECTION (TS) 

 

The Top Section is installed using the same procedure as a Rain 
Cap (CC). 
 
 
 
 
 
 
 
 

Figure 32 – Top Section 

 

EXIT CONE (EXC) 

 

The Exit Cone is installed using the same procedure as the Rain 
Cap (CC). 
 
 
 
 
 
 
 
 

Figure 33 – Exit Cone 

 

HORIZONTAL TERMINATION (HT) 
 

A horizontal termination is used for sidewall termination when 
clearance to combustibles is not an issue such as through a 
concrete wall. The Horizontal Termination includes a bird 
screen which covers the opening to keep birds and rodents 
from entering the system. 

 
 
 
 
 
 
 

 

 

Figure 34 – Horizontal Termination 

 
END CAP (EC)

 

 

The end cap is used to cap off a tee and to allow a means to 
enter the system for inspection and cleaning. The end cap is 
installed by connecting the inner cone to the adjacent pipe 
section with an inner band and sealant. The outer cover piece is 
then fitted over the outer shell and bolted into place with (2)  
¼” x 1 ½” stainless steel bolts. Whenever the end cap is 
removed for inspection purposes the flanges must be cleaned 
and resealed when reinstalling the part. 
 
 
 
 

Summary of Contents for eVent

Page 1: ...sing Boiler Systems A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES AIR SPACES TO COMBUSTIBLE MATERIALS IT IS OF UTMOST IMPORTANCE THAT THIS VENT BE INSTALLED ONLY IN AC...

Page 2: ...ion GS 12 Operating Precautions 13 Maintenance 13 GENERAL These instructions cover installation requirements for the Schebler listed single and double wall special stainless steel venting systems eVen...

Page 3: ...pliance It is recommended that venting systems be enclosed below the roof line to limit condensation and protect against mechanical damage Methods of providing additional insulation may be specified I...

Page 4: ...being vented TERMINATION HEIGHT REQUIREMENTS Vents are to terminate a minimum of 3 ft 0 92 m above the highest point of the roof penetration and 2 ft 0 61m minimum above any portion of a building wit...

Page 5: ...ent eVentPLUS and eVentPLUS2 INDIVIDUAL PART INSTALLATION This section identifies Models eVentSW eVent eVentPLUS and eVentPLUS2 by name and part number or part code See the section titled Part Identif...

Page 6: ...allations install the weld seam along the top of the duct See figure 8 below Step 4 Make a single true cut through both gasket layers Remove excess gasket material and position cut ends such that they...

Page 7: ...W eVent eVent Plus2 has a 1 drain pipe that must be connected to a suitable drain The Drain Tee Cap must be connected at all times to a suitable drain Upon entering the vent rain will wash down and re...

Page 8: ...er band end clips allowing the V to be clamped between the split plates and split clamp flanges Installation for the Wall Support is accomplished with the following procedure 1 Connect the joint to be...

Page 9: ...greatest strength for support of the eVent Series Venting System It will provide vertical support and will provide for joint alignment and support for horizontal applications Locate and secure the Sup...

Page 10: ...following procedure should be used 1 Install the Rain Cap on the inner flange and attach the V band using the inner joint instructions 2 Install the provided skirt section as shown below 3 Apply a sil...

Page 11: ...Section While 3 guys are usually sufficient it is recommended that 4 equally spaced wires at an angle of 45 from the vertical be utilized The cables and guys must be slightly loose to allow for the th...

Page 12: ...located at a joint connection The Guy Section is comprised of four 4 half flanges and is bolted together as shown in figure 39 below with the supplied hardware The outer shell is then sealed by using...

Page 13: ...ANCE Venting and Exhaust Systems 1 After the installation of the vent or exhaust system ensure that the required clearances are maintained and that the system continues to be supported properly 2 The...

Page 14: ...14 February 2019 5665 Fenno Rd Bettendorf IA 52722 www Scheblerchimney com Phone 563 359 0110 Fax 563 359 8430...

Reviews: