Proper performance and long service life of the Model eVent
Series Venting System requires that the vent be rigidly braced and
supported. Every installation offers unique support and bracing
requirements and the following guidelines will provide minimum
acceptable sizes for the mechanical hardware supplied by others.
When the support plate is bolted to framework 3/8” bolts should
be used in all of the holes on the perimeter of the support plate.
Figure 28 – Support Plate Bracing
INSULATED THIMBLE (IT)
The insulated thimble is used in conjunction with the flashing
and rain collar when clearances to combustibles cannot be
maintained at a roof penetration. The Insulated Thimble should
be dropped through the roof opening. The (4) four tabs will set
upon the roof deck and nailed or bolted down. The flashing is
then set over the Insulated Thimble.
Figure 29 – Insulated Thimble
RAIN CAP (CC)
The Rain Cap provides partial protection from rain and debris.
The Rain Cap is mounted on the end of a standard pipe section
with the use of an inner band. A closure ring is provided to
close off the space between the inner and outer liners. A
minimum clearance of 8 feet (2.44 m) is recommended to
ensure that all exhausted products are dispersed away from
the building and intakes. To install the Rain Cap, the following
procedure should be used:
1.
Install the Rain Cap on the inner flange and attach the
"V" band using the inner joint instructions.
2.
Install the provided skirt section as shown below.
3.
Apply a silicone sealant to fill all gaps and joints on the
collar and tighten all bolts.
Figure 30 – Rain Cap Assembly
To clean the flue or replace the Rain Cap, reverse the above
procedure. To reinstall, follow the installation procedure.
5" - 20"
2 x 2 x 3/16
22" - 36"
3 x 3 x 1/4
6 x 2 x 3/8 or
equivalent
38" - 48"
4 x 4 x 3/8
eVent Series Size
Framework
Bracing
5 x 2 x 3/16 to 6 x 2 x
3/16 or equivalent
2 x 1 x 3/16 to 5 x 2 x
3/16 or equivalent
eVent SERIES SUPPORT LIMITS
SECTION INSIDE
DIA.
SUPPORT PLATE (SP)
WALL SUPPORT (WS)
inches mm feet meters feet meters
5-6 127-152 403 122.83 193 58.83
7-8 178-203 389 118.60 171 52.12
9-10 228-254 375 114.36
164 49.99
11-12 279-305 361 110.12
153
46.63
13-14 330-356 347 105.89
148
45.11
15-16 381-406 334 101.65
140
42.67
17-18
431-457
320 97.41 134 40.84
19-20
482-508
306 93.18 129 39.32
21-22
533-559
292 88.94 123 37.49
23-24
584-610
278 84.70 119 36.27
25-26
635-660
264 80.47 113 34.44
27-28
686-711
250 76.23 108 32.92
29-30
736-762
236 71.99 103 31.38
31-32
787-813
222 67.76 120 36.58
33-34
838-864
208 63.52 114 34.75
35-36 889-914 195
59.28
88
26.82
37-38 940-965 181
55.05
81
24.69
39-40 990-1016 167
50.81
77
23.47
41-42 1041-1067 153
46.57
73
22.25
43-44 1092-1118 139
42.34
68
20.73
45-46 1143-1168 125
38.10
64
19.51
47-48 1194-1219 111
33.86
60
18.29