Volumetric flow controller VAQS

®

08/23 - 3

Construction subject to change.

No return possible!

09.05.2019

Version:

Description

The VAQS

®

 volumetric flow controller impresses with its simple

design, high measuring precision and short length, meeting the
majority of customary requirements of volumetric flow control-
lers.

The  volumetric  flow  controller  allows  the  volumetric  flow  in
ducts to be kept constant or to be regulated using positive con-
trol V

min

, V

max

, "OPEN" or "CLOSED". The volumetric flow con-

troller can also be used as a room or duct pressure regulator. In
VAV systems the volumetric flow controller can regulate varia-
ble volumetric flows between V

min

 and V

max

 as a function of the

supply air (room temperature controller). The volumetric flow
setpoints V

min

 and V

max

 can also be altered at the controller at

a later stage, even after installation. Setpoints are initially set in-
factory according to the customer's requirements. If these val-
ues are set ex factory, the functions of the volumetric flow con-
troller are also  checked. The V

min

 and  V

max

  values can range

from 0 to 100 % (with V

min

) and 30 to 100% (with V

max

). The

measuring deviation is ± 5 %, based on V

nom

. Volumetric flow

controllers are in general insensitive to the inflow, owing to the
built-in measuring rods. 6 measuring points are distributed on
these measuring rods according to the median line method. In
comparison  with  measuring  rods having only  four measuring
points or measuring orifices, this gives optimum measurement
results.
When using the controllers in systems with heavy dust contam-
ination, suitable filters must be connected upstream. For pollut-
ed  air,  the  volumetric  flow  controllers  must  be  used  with  an
integrated controller with a static membrane pressure sensor. In
this case, it is absolutely necessary to observe the mounting po-
sition. 

The volumetric flow controllers are not suitable for air con-
taining sticky and greasy components.

For maintenance, service, retrofitting, etc., inspection openings
in sufficient number and size must be provided on site.

- simple design in accordance with the nominal size of the air

duct.
This simple design saves a lot of time and provides planning
safety.

- high controlling precision

Due to its high controlling precision, the controller requires a
straight flow section of only 1 x D even after bends.

- Blades sealing airtight to DIN EN 1751, Class 3
- Housing leakage air flow to DIN EN 1751, class B
- Damper axle support made of maintenance-free plastic
- in-factory presetting of the controllers

The  controllers  have  been  calibrated  and  preset  in  factory:
this in-factory presetting eliminates later setting operations
on-site. However, if a change must be made later on, the V

min

and V

max

 settings can be simply adjusted using the ZTH-EU

setting device. For the calibration of the controllers, a curve
with a flow rate of 12 m/ sec is available. For constant-volume
volumetric flow controllers, the V

min

 value will be set to the

desired constant-volume value.

- Tamper-proof

Since an on-site change in the volumetric flows can only be
done via the ZTH-EU, the controller is tamper-proof. Simple
rotary potentiometers are not tamper-proof!

- no later on-site volumetric flow controller setting necessary.

By virtue of the in-factory presetting, the on-site builder saves
the  time  required  for  on-site  setting  of  the  volumetric  flow
controllers. Accordingly, the responsibility for setting the vol-
umetric flow controllers is not just passed on to the on-site
builder. This also reduces the on-site time pressure, since the
controllers do not have to be set on-site.

- Functional check possible via the ZTH-EU device.

The  VAQS

®

  volumetric  flow  controllers  have  already  been

checked in-factory for their function. When the amount of air
changes on-site, a functional check can simply be carried out
by using the ZTH-EU device.

- simple change in the amount of air via the ZTH-EU setting de-

vice
If the amounts of air preset in-factory must be adapted on-
site,  this  can  be  simply  done  by  using  the  ZTH-EU  device.
When the controllers are mounted in false ceilings, the ZTH-
EU can be simply inserted, and the setting and check can be
done comfortably inside the room. This is an advantage com-
pared with changing the settings of potentiometers, because
the potentiometers in false ceilings are often hard to get to
and difficult to see. If the changes in air volume are so large
that  the  calibration  curve must  be  changed,  the  controllers
must either be recalibrated in-factory or the calibration curve
must be changed on-site by the customer service of Schako.

- Covers the majority of customary requirements

V

min

, V

max

 and V

konstant

 controls possible, as well as positive

control “Closed“ or positive control “Open“.

- Simple to connect

The controller contains the electrical wiring information. This
avoids wiring faults.

- Protection type IP 54

The controllers have the protection type IP 54. A strain relief
for the cables has been integrated. For lower protection types,
e.g. IP 20, mounting into ventilation systems or central units
is not recommended.

Summary of Contents for VAQS DS0 Series

Page 1: ...Ferdinand Schad KG Steigstra e 25 27 D 78600 Kolbingen Telephone 49 0 74 63 980 0 Fax 49 0 74 63 980 200 info schako de www schako de Volumetric flow controller VAQS...

Page 2: ...cessories 5 Technical data 7 Volumetric flow range 8 Technical data for Belimo components 9 Operating control Belimo components 9 Circuit diagrams 10 Setting the operating potentiometers calculation f...

Page 3: ...mper axle support made of maintenance free plastic in factory presetting of the controllers The controllers have been calibrated and preset in factory this in factory presetting eliminates later setti...

Page 4: ...f several connection pieces or pieces with fire dampers or silencers the larger minimum distances must be observed All volumetric flow controllers can be assembled with horizontal or vertical damper a...

Page 5: ...51 Class 3 Housing leakage air flow to DIN EN 1751 class B with electric controller LMV NMV D3 MF not MP bus ca pable Control voltage 24 V AC 50 60 Hz Temperature compensation from 10 40 C Acoustic cl...

Page 6: ...for VAQS with 1 baffle with 2 baffles with 3 baffles B mm KA K mm S mm De dB Okt fm Hz 63 125 250 500 1000 2000 4000 8000 150 1 100 50 2 6 16 26 48 48 33 15 200 1 100 100 1 3 9 18 36 37 22 13 250 1 1...

Page 7: ...52 63 68 68 67 67 65 63 72 74 74 73 73 71 69 78 81 82 81 81 80 77 86 6 68 67 66 65 63 58 70 73 73 72 71 69 67 76 78 79 78 77 76 74 82 84 85 84 84 84 82 90 9 73 73 73 71 69 65 76 79 78 78 76 75 73 82...

Page 8: ...tomer absolutely wants a calibration curve different from 12 m s it must be specified When the air volume drops below the Vmin shown in the chart the correct functioning of the volumetric flow control...

Page 9: ...ve control CLOSED can be implemented via a diode see page 10 Operating control Belimo components Positive control damper CLOSED Energy saving in areas not in use by closing the supply and re turn air...

Page 10: ...w Function 0 1 V 0 Damper CLOSED VAV control inac tive 0 2 2 V Vmin Vmin operating stage active 2 10 V Vmin Vmax Continuous opera tion Vmin Vmax No Designation Wire colour Function 1 black Feed AC DC...

Page 11: ...viour S2 service function Adaptation Adaptation started by a Operating service unit b Key on the VAV Compact V1 VAV service VAV service active a Press both keys Adaptation Address simultaneously b VAV...

Page 12: ...n of the Vnenn volumetric flow m h The calibration curve is usually 12 m s Upon customer request a smaller value can be selected Actual value measurement via feedback signal U5 using a voltmeter or PC...

Page 13: ...ting range Vmin Vmax Vmin 0 100 of set Vnenn volumetric flow Vmax 30 100 of set Vnenn volumetric flow Command variable Y Input resistance min 100 k DC 2 10 V 4 20 mA with 500 input re sistance DC 0 10...

Page 14: ...C DC converter This is why no external power supply is necessary Driver To be able to work with the ZTH EU a suitable driver must be installed on the PC The driver can be downloaded from the Be limo w...

Page 15: ...tible with all Belimo PP MP units from 1992 efficient handling can be operated with one hand Selection of stages for test OPEN CLOSE MIN MAX STOP Damper position indicator for diagnostics Display of t...

Page 16: ...t personnel observ ing recognised technical rules and regulations 6 For polluted air the volumetric flow controllers must be used with an integrated controller with a static membrane pressure sensor I...

Page 17: ...assembly Mode Volumetric flow Vmin Volumetricflow Vmax Acoustic cladding Damper position Example VAQS 0250 200 DD A007 0 00200 01500 DS2 NA VAQS Volumetric flow controller type VAQS rectangular desig...

Page 18: ...m galvanised sheet steel with METU flange M2 Order details 01 Type 02 Width 03 Height 04 Material 05 Profile connection 01 02 03 04 05 Type Width Height Material Profile connection Example ZSQ 1000 04...

Page 19: ...IN EN 1751 class B made of aluminium Meas uring rods made of aluminium blade support made of plastic With electric controller LMV NMV D3 MF control voltage 24 V AC 50 60 Hz requirement measuring air 0...

Reviews: