Volumetric flow controller VAQS

®

08/23 - 9

Construction subject to change.

No return possible!

09.05.2019

Version:

Technical data for Belimo components

Measured value collection and control function

The measured values are collected by two measuring rods fa-
vourable  to the  flow. The measuring  openings are  distributed
over the measuring rods according to the median line method.
The pressure differential formed on the measuring rods is deter-
mined by means of a dynamic or static measuring sensor. From
these measuring results the middle value is formed, which gives
a measured variable for the volume flow. The controller com-
pares the actual value signal with the set point and sends a start
signal to the electric actuator which adjusts the controller devi-
ation independent of pressure changes in the duct network.

Attention:

The volumetric flow controllers equipped with the Belimo con-
trol  type  LMV/NMV-D3-MF  are  delivered  as  standard  with  a
SCHAKO 2 - 10 V DC drive (w-signal). Upon activation with 2 V
DC, the V

min

 volume is set. The V

min

 volumes can be seen from

the V

min

 / V

max

 tables. When the V

min

 volume drops below the

values shown in the V

min

 / V

max

 table, then the control function

and the output of the U5 signal is no longer guaranteed for me-
trology reasons. Airtight sealing to DIN 1751 can be achieved by
means of a 0V actuator signal or via a positive control. This pos-
itive control "CLOSED" must be implemented on-site via a switch
contact.

Upon customer request, the volumetric flow controller equipped
with the Belimo control type LMV/NMV-D3-MF can also be de-
livered with the drive 0-10 V DC. However, please note that in
this case the positive control "CLOSED" can be implemented via
a diode, see page 10. 

Operating control Belimo components

Positive control damper "CLOSED"

Energy saving in areas not in use by closing the supply and re-
turn air volumetric flow controller. If the input Y is connected to
terminal 1 (see page 10) via an on-site switch for the 

operating

range 2-10 V DC

, the drive will move the damper to the 

CLOSED

position

. The drive will also close the damper if the setpoint val-

ue for the minimum volumetric flow V

min

 has been set to 0%,

and the control signal corresponds to the value V

min

. This func-

tion  does  not  correspond  to  the  function  of  positive  control
"CLOSED" via the switch contact.

Positive control damper "OPEN"

Supports smoke extraction or is used as a safety position. The
volumetric flow controller is in this case inactive, and the damp-
er is driven to the mechanical open position.

V

min

 control to min. volumetric flow

Depending on requirement or by not assigning them, individual
areas can be set to stand-by operation. In this way, minimum
room  flushing  with  greatly  reduced  energy  expenditure  is
achieved.

V

max

 control to max. volumetric flow

Individual or several rooms are supplied for a short period  with
a  maximum  volumetric flow. This allows  airing,  night  cooling
and quick heating to be implemented.

Continuous operation

As a function of the continuous command signal and the pro-
grammed operating area (2 - 10 V; 0 - 10 V) the LMV/NMV-D3-
MF will regulate the volumetric flow between the set values of
V

min

 and V

max

.

Constant operation

If terminal 3 (Y signal) has not been assigned, the air volume set
on the V

min

 potentiometer will be set to a constant volume.

VAV-Compact (LMV/NMV-D3-MF)

The  operation  control  is  effected  via  the  drive  input  w/z.  The
possible functions depend on the selected operating mode "2-10
V" or "0-10 V" The diagrams below show the possible settings.

Summary of Contents for VAQS DS0 Series

Page 1: ...Ferdinand Schad KG Steigstra e 25 27 D 78600 Kolbingen Telephone 49 0 74 63 980 0 Fax 49 0 74 63 980 200 info schako de www schako de Volumetric flow controller VAQS...

Page 2: ...cessories 5 Technical data 7 Volumetric flow range 8 Technical data for Belimo components 9 Operating control Belimo components 9 Circuit diagrams 10 Setting the operating potentiometers calculation f...

Page 3: ...mper axle support made of maintenance free plastic in factory presetting of the controllers The controllers have been calibrated and preset in factory this in factory presetting eliminates later setti...

Page 4: ...f several connection pieces or pieces with fire dampers or silencers the larger minimum distances must be observed All volumetric flow controllers can be assembled with horizontal or vertical damper a...

Page 5: ...51 Class 3 Housing leakage air flow to DIN EN 1751 class B with electric controller LMV NMV D3 MF not MP bus ca pable Control voltage 24 V AC 50 60 Hz Temperature compensation from 10 40 C Acoustic cl...

Page 6: ...for VAQS with 1 baffle with 2 baffles with 3 baffles B mm KA K mm S mm De dB Okt fm Hz 63 125 250 500 1000 2000 4000 8000 150 1 100 50 2 6 16 26 48 48 33 15 200 1 100 100 1 3 9 18 36 37 22 13 250 1 1...

Page 7: ...52 63 68 68 67 67 65 63 72 74 74 73 73 71 69 78 81 82 81 81 80 77 86 6 68 67 66 65 63 58 70 73 73 72 71 69 67 76 78 79 78 77 76 74 82 84 85 84 84 84 82 90 9 73 73 73 71 69 65 76 79 78 78 76 75 73 82...

Page 8: ...tomer absolutely wants a calibration curve different from 12 m s it must be specified When the air volume drops below the Vmin shown in the chart the correct functioning of the volumetric flow control...

Page 9: ...ve control CLOSED can be implemented via a diode see page 10 Operating control Belimo components Positive control damper CLOSED Energy saving in areas not in use by closing the supply and re turn air...

Page 10: ...w Function 0 1 V 0 Damper CLOSED VAV control inac tive 0 2 2 V Vmin Vmin operating stage active 2 10 V Vmin Vmax Continuous opera tion Vmin Vmax No Designation Wire colour Function 1 black Feed AC DC...

Page 11: ...viour S2 service function Adaptation Adaptation started by a Operating service unit b Key on the VAV Compact V1 VAV service VAV service active a Press both keys Adaptation Address simultaneously b VAV...

Page 12: ...n of the Vnenn volumetric flow m h The calibration curve is usually 12 m s Upon customer request a smaller value can be selected Actual value measurement via feedback signal U5 using a voltmeter or PC...

Page 13: ...ting range Vmin Vmax Vmin 0 100 of set Vnenn volumetric flow Vmax 30 100 of set Vnenn volumetric flow Command variable Y Input resistance min 100 k DC 2 10 V 4 20 mA with 500 input re sistance DC 0 10...

Page 14: ...C DC converter This is why no external power supply is necessary Driver To be able to work with the ZTH EU a suitable driver must be installed on the PC The driver can be downloaded from the Be limo w...

Page 15: ...tible with all Belimo PP MP units from 1992 efficient handling can be operated with one hand Selection of stages for test OPEN CLOSE MIN MAX STOP Damper position indicator for diagnostics Display of t...

Page 16: ...t personnel observ ing recognised technical rules and regulations 6 For polluted air the volumetric flow controllers must be used with an integrated controller with a static membrane pressure sensor I...

Page 17: ...assembly Mode Volumetric flow Vmin Volumetricflow Vmax Acoustic cladding Damper position Example VAQS 0250 200 DD A007 0 00200 01500 DS2 NA VAQS Volumetric flow controller type VAQS rectangular desig...

Page 18: ...m galvanised sheet steel with METU flange M2 Order details 01 Type 02 Width 03 Height 04 Material 05 Profile connection 01 02 03 04 05 Type Width Height Material Profile connection Example ZSQ 1000 04...

Page 19: ...IN EN 1751 class B made of aluminium Meas uring rods made of aluminium blade support made of plastic With electric controller LMV NMV D3 MF control voltage 24 V AC 50 60 Hz requirement measuring air 0...

Reviews: