6.4 Vibrations 

The fan is factory-balanced to minimise 
vibrations during operation. If 
vibrations occur, it usually indicates 
accumulation of dust and dirt on the 
impeller system. If the problem remains 
after ordinary cleaning, please contact 
professional assistance. Continuous 
operation with vibrations may damage 
both motor bearings and impeller.
Check the vibration dampers in the 
suspension brackets for ruptures and 
replace the dampers at signs of ruptures.

6.5 Motor

The motor has closed bearings that 
should be changed in accordance with 
the motor supplier's recommendations.

6.6 Removal of motors

Before start, follow the procedure in 
section 

“6.1 

Safety measures

.

Novenco recommends the use of a lift 
and that only the motor arrangement is 
taken down, instead of the entire fan 
unit.

Removal of motors

1 Loosen the external motor cable 

connector.

2 Remove the terminal box cover plate 

and take out the terminal box. Turn 
and affix the cover with a single screw 
to the fan casing to facilitate work on 
the terminal box (fig. 6).

3 Disconnect the motor cable in the 

terminal box and loosen the internal 

cable connector (1, fig. 7) at the 
separation from the pressure 
chamber. Push the cable fully into the 
pressure chamber.

4 Prepare support of the motor 

arrangement, e.g., with a lift, in order 
to lift it as short as possible and 
preferably straight down.

5 Loosen the motor arrangement (eight 

M8x16) (1, fig. 8) from the fan casing 
and take it down.
The arrangement requires two people 
to take down safely. Make sure to pull 
the motor cable completely free of the 
fan casing.

6 Leave the wire guard affixed to the 

inlet nozzle (2, fig. 8).

7 Remove the impeller by removing the 

motor shaft screw (3, fig. 8).

8 Disconnect the motor from the inlet 

nozzle. It is attached with eight 12x20 
screws (4, fig. 8).

9 Slide the steel tube off the motor cable.

The motor is now ready for service. Refer 

to the motor supplier’s instructions for 

service.

6.7 Mounting of motors

Lubricate bolts with grease, before 
screwing them in during reassembly.

Mounting of motors

1 Slide the steel tube onto the cables for 

the new motor.

2 Affix the motor to the inlet nozzle 

with the eight 12x20 screws (4, fig. 8).

3 Install the impeller on the inlet nozzle 

and attach it to the motor shaft.

4 If the wire guard has been removed, 

then affix it to the inlet nozzle with 
four blind rivets 3.2x10 of stainless 
steel grade A2 (2, fig. 8).

5 Support and place the motor 

arrangement in the fan casing. Make 
sure to pull the motor cable along the 
same route as from the factory.
The arrangement is attached with 
eight M8x16 screws (1, fig. 8).

6 Roll the motor cable up into the 

terminal box room, before tightening 
the connector at the separation from 
the pressure chamber.

7 Connect the motor cable in the 

terminal box and install it and the 
cover (fig. 6).

8 Tighten the external motor cable 

connector.

9 Connect the power supply for the fan 

and follow the procedure in section 

“5.2 

Start procedure

.

Figure 7.

Loosen internal connector

1

Figure 8.

Removal of motor

2

1

4

3