7. Inspection and test

Extent of inspection

• Measure power consumption at full 

and half speeds

• Vibration measuring on fan casing 

(outside motor)

• Check of fan suspension
• Visual inspection of rotor, casing, si-

lencers and electric connection

• Cleaning

– Internal with compressed air or 

vacuum cleaning

– External with a wrung cloth. No 

water must get in the electric sys-
tems or the acoustic insulation.

Keep a journal of all measured values 
and observations for each fan.

8. Sound

The fan sound emission depends on in-
stallation and operating conditions, 
hence no general data can be given.
Refer to the product catalogue and the 
technical fan specifications.

9. Safety

The jet fans must be installed according 
to Novenco’s, the current and the local 
safety regulations. At a minimum these 
include EN 13850.
It is recommended to review and revise 
safety procedures regularly.

Safety check

• Test if safety procedures and the in-

stallation work correctly.

• Check if safety regulations have been 

changed and if the installation needs 
revising.

• Consider taking additional measures 

to improve the safety of the installa-
tion. For example, by mounting wire 
guards on inlet and outlet.

10. Spare parts

Contact Novenco for information about 
and ordering of spare parts.

Summary of Contents for NOVENCO ARO 290

Page 1: ...Pure competence in air 919044 0 AUO ARO ARP AUZ AUT ART AZT INSTALLATION AND MAINTENANCE ENGLISH ...

Page 2: ...must not be used in these kinds of environments 3 Handling 3 1 Marking The fans are fitted with nameplates with manufacturing information such as product type e g AUO 380 160 4 serial and order numbers max RPM weight production year and CE marking Nameplateson jetfans forsmokecontrol include additional data such as air per Type Temperatures Air 20 to 55 C Environment 20 to 55 C Fire F200 200 C for...

Page 3: ...e that these are optional and not part of standard deliveries Arrows on the fans indicate the airflow direction and rotation Within a smoke reservoir the jet fans must be fastened to non flammable ma terials only and must meet current na tional requirements In general the jet fans must be mounted so that there is no risk of them falling down in case of fire If unapproved expansion bolts for high t...

Page 4: ...s 5 5 Approval for operation The installation must be approved with regard to operation and interaction The person responsible for the operation of the system must initiate this test The approval test must be confirmed The person responsible for the operation of the system must keep the approval testdocuments Forjetfansapprovedfor smoke control the documents must be presented upon request from aut...

Page 5: ... are disconnected 6 3 Cleaning Cleanfansandsilencerswhenneededby means of pressurised air or vacuum cleaning 6 4 Vibrations Fromthefactory thefansarebalancedto run without vibrations Vibrations occurring during operation are normally an indication of accumula tion of dust and dirt or foreign bodies on the rotor system If ordinary cleaning does not solve the problem the fans must stay off line and ...

Page 6: ...and that the motor shaft is centred in the fan casing before tightening the set screws item 08 AUZ and AZT Check that the motor shaft is centred in the fan casing before tightening the bolts items 14 3 Mount the rotor item 07 on the motor shaft by means of a jack fastened in the threaded hole of the motor shaft Press the rotor hub to contact against the motor shaft collar Important Do NOT use hamm...

Page 7: ... and operating conditions hence no general data can be given Refer to the product catalogue and the technical fan specifications 9 Safety The jet fans must be installed according to Novenco s the current and the local safety regulations At a minimum these include EN 13850 It is recommended to review and revise safety procedures regularly Safety check Test if safety procedures and the in stallation...

Page 8: ...7670 and Denmark no PR 1774428 Granted designs include EU no 001069884 0001 to 001069884 0028 Other trademarks appearing in this document are the property of their respective owners Copyright 1985 2018 Novenco Building Industry A S All rights are reserved 12 Quality management Novenco is ISO 9001 and 14001 certified All fans are inspected and tested before leaving the production 13 Warranty Novenc...

Page 9: ...Pure competence in air WWW NOVENCO BUILDING COM ...

Reviews: