background image

2

formance data, max. temperature, work-
ing period, category/class according to 
relevant standards and regulations.
A motor plate with relevant data is on 
the side of the fan casing.
Documentation and instructions from 
the motor manufacturer are included 
with the fan. Save them for when the fan 
is serviced.

3.2 Weights

3.3 Transport

The jet fans are delivered on pallets to al-
low for forklift handling. Avoid making 
deformations of the fan casings.

4. Storage

The jet fans are unsuited for outdoor 
storage.
If the fans are stored indoors under well-
ventilated conditions with no risk of con-
densation, the storage period is 
6 months.
The storage space must not be exposed to 
vibrations likely to damage the motor 
bearings. If the storage period exceeds 
3 months, it is recommended to turn the 
rotor regularly.
Check the fans for damages and corro-
sion prior to installation. Before start of 
operation, make sure there is no conden-
sate in the motor.

5. Installation

5.1 Before installation

Make sure that the rotor rotates freely 
with equal distance between blade tips 
and fan casing throughout the circum-
ference.

AUO/ARO:

 Remove the transport 

brackets on the underside of the fan 
housing after installation. The brackets 
have yellow labels. Insert the screws 
from the brackets again, as these secure 
the casing.

5.2 Installation

Install the jet fans so that there is at least 
0.5 m to the nearest obstruction on the in-
let side and at least 2 m on the outlet side 
for unidirectional fans. For reversible 
fans there must be 2 m on either side of 
the fans.

Lower the fan correspondingly for ob-
structions higher than the installation 
height (H).

Fasten the fan in each of the suspension 
points to the ceiling or the lowering 
brackets. It is recommended to install vi-
bration dampers as shown in figure 3b or 
3c. Please note that these are optional 
and not part of standard deliveries.
Arrows on the fans indicate the airflow 
direction and rotation.
Within a smoke reservoir the jet fans 
must be fastened to non-flammable ma-
terials only and must meet current na-
tional requirements. In general, the jet 
fans must be mounted so that there is no 
risk of them falling down in case of fire.
If unapproved expansion bolts for high 
temperature are used, these must be 
made from steel, must at least be size M8 
and must be mounted twice as deep as 
recommended – at least 60 mm deep. 
The static load must not exceed a pull of 
more than 500 N.
Expansion bolts certified for fire condi-
tions must be mounted and loaded ac-
cording to the approval.

The jet fans must be fixed to a horizontal 
plane with a natural frequency at least 
20% from the fan speed.
After final installation, check that the 
rotors rotate freely in the fan casings.
It is essential for the performance and 
sound level that the airflow is unimped-
ed and free from eddies.

Weights [kg]

AUO/ARO size 290

80

AUO/ARO size 380

110

AUO/ARO size 500

160

ARP size 340

100

AUZ size 340

78

AUT/ART size 400

63

AZT 450

70

Table 2.

 Unit weights

Figure 2.

 Principle installation

H

A

B

C

AUO/ARO 290

320 506 560 4 x ø14 M12

AUO/ARO 380

420 506 720 4 x ø14 M12

AUO/ARO 500

540 600 830 4 x ø14 M12

ARP 340

422 283 520 4 x ø14 M12

AUZ 340

422 283 520 4 x ø14 M12

AUT/ART 400

423 779 470 4 x ø14 M12

AZT 450

540 540 260 4 x ø11 M10

Table 3.

 Mounting specifications

Figure 3a.

 Installation of jet fans

Item 01 Jet fan
Item 02 Expansion bolt
Item 03 Ceiling

01

02

03

B

A

C

H

500

500*

500

500*

* Minimum 500 mm
free for air intake

Detail
figure 3b

Detail
figure 3b

Use lowering brackets
in areas with high beams

Bottom jetfan = beam height

Figure 3b.

 Example of ceiling installation 

with vibration dampers

Figure 3c.

 Example of ceiling installation 

with vibration dampers for AZT

Vibration
dampers
Disc
Concrete
screw 10x130

Steel pipe

Steel pipe

Vibration
dampers

Disc

Concrete
screw 10x130

Summary of Contents for NOVENCO ARO 290

Page 1: ...Pure competence in air 919044 0 AUO ARO ARP AUZ AUT ART AZT INSTALLATION AND MAINTENANCE ENGLISH ...

Page 2: ...must not be used in these kinds of environments 3 Handling 3 1 Marking The fans are fitted with nameplates with manufacturing information such as product type e g AUO 380 160 4 serial and order numbers max RPM weight production year and CE marking Nameplateson jetfans forsmokecontrol include additional data such as air per Type Temperatures Air 20 to 55 C Environment 20 to 55 C Fire F200 200 C for...

Page 3: ...e that these are optional and not part of standard deliveries Arrows on the fans indicate the airflow direction and rotation Within a smoke reservoir the jet fans must be fastened to non flammable ma terials only and must meet current na tional requirements In general the jet fans must be mounted so that there is no risk of them falling down in case of fire If unapproved expansion bolts for high t...

Page 4: ...s 5 5 Approval for operation The installation must be approved with regard to operation and interaction The person responsible for the operation of the system must initiate this test The approval test must be confirmed The person responsible for the operation of the system must keep the approval testdocuments Forjetfansapprovedfor smoke control the documents must be presented upon request from aut...

Page 5: ... are disconnected 6 3 Cleaning Cleanfansandsilencerswhenneededby means of pressurised air or vacuum cleaning 6 4 Vibrations Fromthefactory thefansarebalancedto run without vibrations Vibrations occurring during operation are normally an indication of accumula tion of dust and dirt or foreign bodies on the rotor system If ordinary cleaning does not solve the problem the fans must stay off line and ...

Page 6: ...and that the motor shaft is centred in the fan casing before tightening the set screws item 08 AUZ and AZT Check that the motor shaft is centred in the fan casing before tightening the bolts items 14 3 Mount the rotor item 07 on the motor shaft by means of a jack fastened in the threaded hole of the motor shaft Press the rotor hub to contact against the motor shaft collar Important Do NOT use hamm...

Page 7: ... and operating conditions hence no general data can be given Refer to the product catalogue and the technical fan specifications 9 Safety The jet fans must be installed according to Novenco s the current and the local safety regulations At a minimum these include EN 13850 It is recommended to review and revise safety procedures regularly Safety check Test if safety procedures and the in stallation...

Page 8: ...7670 and Denmark no PR 1774428 Granted designs include EU no 001069884 0001 to 001069884 0028 Other trademarks appearing in this document are the property of their respective owners Copyright 1985 2018 Novenco Building Industry A S All rights are reserved 12 Quality management Novenco is ISO 9001 and 14001 certified All fans are inspected and tested before leaving the production 13 Warranty Novenc...

Page 9: ...Pure competence in air WWW NOVENCO BUILDING COM ...

Reviews: