Fire-resistant damper model BKA-Ü
Technical documentation
Installation in lightweight partition walls with metal posts
Construction subject to change
No return possible
Version: 2021-07-01 | Page 15
Installation procedure
Mount the metal posts and the wall in accordance with the
specifications of the wall manufacturer and the required ex-
change parts as shown on Figure 14.
Provide a recess for the wet installation of BKA-Ü (pos. 1)
From B > 800 mm (with horizontal damper blade axle), on
both B sides of the exchange profiles, 2 bent perforated
plates each (t ≥ 0.5 mm; width x length = 40 x 70 mm), must
be fastened as mortar anchor (pos. 14). They must be
screwed to the metal profiles at the wall centre, using one
dry-wall screw for each plate.
Insert the BKA-Ü into the wall recess (operating side - ob-
serve the installation dimension of 210 mm). Average out
the circumferential annular gap evenly between the wall
and BKA-Ü. Mounting of BKA-Ü with the help of mounting
suspensions etc.
Insert mortar (pos. 13) into the circumferential gap of 40
mm between the BKA-Ü housing and the circumferential
metal profiles (pos. 10). If reveals (pos. 20) are used, a mor-
tar bed depth of 100 mm is sufficient. When using reveals,
the exchange parts must be adjusted to the recess dimen-
sions.
1 Fire-resistant damper model BKA-Ü
9 Profile CW 50/50/06 (with wall thickness = 100 mm, for
larger wall thicknesses, the profiles must be adapted
accordingly)
10 Profile UW 50/40/06 (with wall thickness = 100 mm, for
larger wall thicknesses, the profiles must be adapted
accordingly)
11.1 Mineral wool (according to the wall manufacturer's
specifications)
12 Panelling of the metal post wall made of gypsum-bonded
wall boards
13 Mortar
14 From B>800 mm, 2 mortar anchors for each B side are
required, for installation with horizontal damper blade
axle (perforated plate t
≥
0.5 mm; width x length = 40 x
70 mm; accessories at an extra charge).
16 Solid ceiling
20 Reveal, optional
33.1 Dry-wall screws (-on site- e.g. ø 3.5 x 25 mm)
same quantity as mortar anchors (pos. 14)
48 Thermal insulation