Schaffner Group
User and Installation Manual
Ecosine
max
59/66
8.3.8 Install and connect the switch remote operator
(only relevant for filter with switch option, see sections
2.1 to 2.4 and with addition of remote operator module)
The remote operator for the switch allows to control remotely
the switch on order when required for the application.
The remote operator module is not provided by Schaffner
and when required, it need to be bought separately. Please
consult the relevant user manual
and usage.
Warning: the switch is a protection device; its
purpose is to disconnect the trap capacitor circuit in
case of over-current or over-heating. Usage of the
switch with or without remote operator is never in-
tended for frequent manual or on order opening (e.g.
NZM 3 series allows only 2000 on load openings in its
lifetime, please consult the switch manual
formation). For frequent commutation, the addition of a
capacitor contactor in series with the switch circuit
breaker is strongly recommended. Please refer to sec-
tion 10 for more details.
Figure 32 Eaton switch remote opera-
tor module
i
Online datasheet and documentation for