Schaffner Group
User and Installation Manual
Ecosine
max
14/66
2.1 Filter selection tables FN 3470/FN 3471 (50 Hz, 3×380 … 415 VAC)
Table 3 FN 3470 filter selection table for models with circuit breaker
Filter
Rated
load
power
@ 400V
/50 Hz
Motor
drive
input
current
Rated
filter
input
cur-
rent
Typi-
cal
power
losses
@
40°C
Circuit
breaker
rated
current
Weigh
t
Termi-
nal
Fram
e
size
[kW]
[Arms]
[Arms]
[W]
[A]
[kg]
FN 3470-250-99-
E0XXSXX
250
435
376
3029
250
270
Busbar
S10
FN 3470-315-99-
E0XXSXX
315
655
475
3295
250
295
Busbar
S10
FN 3470-355-99-
E0XXSXX
355
727
538
3527
300
320
Busbar
S12
FN 3470-400-99-
E0XXSXX
400
808
608
4617
400
426
Busbar
L10
FN 3470-500-99-
E0XXSXX
500
985
766
4475
400
510
Busbar
L12
*Motor drive input current without harmonic filter.
Table 4 FN 3470 filter selection table for models with trap disconnect jumper
Filter
Rated
load
power
@ 400V
/50 Hz
Motor
drive
input
current
Rated
filter
input
cur-
rent
Typi-
cal
power
losses
@
40°C
Weight
Terminal
Frame
size
[kW]
[Arms]
[Arms]
[W]
[kg]
FN 3470-250-99-
E0XXJXX
250
435
376
3029
270
Busbar
S10
FN 3470-315-99-
E0XXJXX
315
655
475
3295
295
Busbar
S10
FN 3470-355-99-
E0XXJXX
355
727
538
3527
320
Busbar
S12
FN 3470-400-99-
E0XXJXX
400
808
608
4617
426
Busbar
L10
FN 3470-500-99-
E0XXJXX
500
985
766
4475
510
Busbar
L12
*Motor drive input current without harmonic filters.