496330 Issue 1
5 of 10
3.
Key-in the factory default engineer code, “0” followed by “ENTER” then
“7890”. The “Fault” and ”Service” LEDs will flash and the internal
sounder will be bleeping.
4.
Open the control panel or end station lid. The internal sounder stops
bleeping and the “Service” LED will be steady. Make connections to
AUX power, stand-by battery and connections to SAB. Proceed to
program the system.
Note: If an SAB/SCB module is fitted within the bell, it will continue to ring until the
panel supply is connected and until the bell cover lid tamper switch is closed.
Programming Commands
To change the factory default program, use the commands listed in this
section as follows:
1.
Enter the command number.
2.
Enter one or more digits to give the new program.
3.
Press ENTER.
The panel will give a double bleep to show that it has accepted the
command. If you enter the command incorrectly the panel gives a single
tone.
Default Settings
When delivered from the factory, the panel is programmed as follows:
Zone 1, Entry Route Part Set zone.
01 36
Zone 2, Normal alarm, active in Part Set, Omit allowed.
02 16 OMIT
Zone 3, Normal Alarm, active in Part Set, Omit allowed.
03 16 OMIT
Zone 4, Normal Alarm, active in Part Set, Omit allowed.
04 16 OMIT
Zone 7(E/E) part set.
07 6
User code
1234
Engineering Program Commands
To change
Key in:
Followed by + ENTER
Zones 1-4
01-04
0 = Not used
1 = Normal Alarm
2 = 24 Hour Alarm
3 = Entry Route
4 = Double Knock
5 = Chime
6 = Part set zone
OMIT = Omit Allowed
9452/3
Programming Commands