To change
Key in: Followed by:
+ ENTER
Zones 1-6
01-06
0= Not used
1= Normal Alarm
2 = 24 Hour Alarm
3 = Entry Route
4 = Entry/Exit
5 = PA
6 = Fire Alarm
7 = Technical Alarm
In addition:
8 = Chime
9 = Active in Part Set
OMIT = Omit Allowed
Strobe Output
11
Reserved. Do Not Use
Programmable Output 1
12
18 = PIR Set Latch (+ve applied when
active)
19 = +ve removed when active. Not
normally used
28 = Shock Sensor Reset (+ve removed
when active)
29 = +ve applied when active. Not
normally used
3 = Reserved
48 = Not normally used
49 = Strobe (-ve switched)
58 = +ve removed when active. Not
normally used
59 = Internal Alarm (+ve applied when
active)
Engineer Access
20
Any 4 digit code
Key Switch Operation
21
0 = Momentary
1 = Latched
PA
30
0 = Audible Alarm
1 = Silent Alarm
System Reset
31
0 = Customer Reset
1 = Engineer Reset
2-Ply Entry Timer
32
0 = Disabled
1 = Enabled
Keypad PA
33
0 = Disabled
1 = Enabled
Set/Part Set Display
34
0 = LEDs ON when set and part set
1 = LEDs OFF when set and part set.
Exit Mode
35
0 = Timed or Terminated
1 = Final Door Set
Rearm
40
0 = Never
1 = Once
2 = Twice
3 = Three times
4 = Always
20
Pr
ogramming
496219 Issue 1
Example:
To select Shock Sensor
Reset key in 12 28 and
then press ENTER.
Example:
Select one zone type from
0 to 7.
Choose which attributes
you require from 8, 9 and
OMIT.
Then press ENTER.
601 installation 23/10/1998 10:09 Page 20