Storage Battery Systems, Inc. MANUAL PSC
20
I ph3 (setting value)
17
2
R
Status Alarm Rectifier Fail
18H
1
R
Status Alarm High Volt
18L
1
R
Status Alarm low Volt
19H
1
R
Status Alarm neg ground
19L
1
R
Status Alarm pos ground
20H
1
R
Status Alarm AC Fail
20L
1
R
Status Alarm HV Shut Down
21H
1
R
Status Alarm Low Volt Disc
21L
1
R
Status Alarm AC high volt
22H
1
R
Status Alarm AC low volt
22L
1
R
Status Alarm High external
temperature
23H
1
R
Status Alarm low external
temperature
23L
1
R
Status Alarm High temperature of
card
24H
1
R
Status Alarm Battery Discharging
24L
1
R
Status Alarm I Lim
25H
1
R
Status Alarm Equalize
25L
1
R
Status Alarm cut fuse
26H
1
R
Not Used
26L
X
X
Mode Equalize/Float
27
2
W/R
Reset Alarms
28
2
W
Password
29
2
W
Table 1
Note:
Reading the value “
FF
(HEX)
” at any “Status Alarm” (setting value or mode)
address means that this alarm (setting value or mode) has not been ordered with
your charger.
1.1 - Format for voltage and current values :
Voltage and current values are coded on 2 bytes :
Example:
V
out
= 651.3V (6513 decimal = 1971 hex),
so the coded value will be :