Storage Battery Systems, Inc. MANUAL PSC
14
Reset alarms and relays:
(available in case of alarm only)
DISPLAY
Press
ACTION
Reset relays
Yes
No
Reset all the relays
Go to Reset alarm
Reset Alarm msg
(not displayed)
Yes
No
Clear all alarms messages
Go to Relay test
Relay Test
(not displayed)
Yes
No
Test all relays
Go back one level
Adjust:
Use
à
or
ß
keys to scroll the sub-menus.
SET
to enter menu.
EXIT
to return to previous menu.
DISPLAY
Press
ACTION
PASSWORD
F2-F1-F3 (Push in order)
EXIT
Enter Level 1
Return to previous menu
Password must be valid to access
Control, Alarms and reading sub-menu
Control?
SET
Go to Control adjustments
Alarms?
SET
Go to alarm adjustments
Level 2?
SET
Go to level 2 sub-menu
Control:
Use
à
or
ß
keys to scroll the Control sub-menus.
SET
to enter menu.
EXIT
to return to previous menu.
DISPLAY
Press
ACTION
Default Value
Float
+ or -
Adjust Float Voltage (V)
Vnom X 1.09
I LIM
+ or -
Adjust Current Limit (A)
Eq
SET
+ or -
Toggle On/Off Equalization Voltage
Adjust Equalization Voltage (V)
On
Vnom X 1.12
T eq
+ or -
Adjust Equalization Time (Hour)
L VEQ
+ or -
Adjust Low Equalization Voltage (V)
Vfloat X 0.85
TA LIM E
+ or -
Adjust Time/Current limit Equalization
(Minute)
5 min
ACEq
SET
Toggle On/Off AC Equalization
On
Tfloat
+ or -
Adjust Float Timing (Days)
28 Days