background image

Page | 10  

 

Vent Caps 

Ensure that the transport seal film used for preventing electrolyte spillage during transportation has been removed from the vent caps 
before charging. 

The cell vent caps should be closed during charging.  

Vent caps should be kept clean to allow venting of gases produced during charging.  Wash ceramic plugs, if soiled, in clean water and 
dry them thoroughly before putting them back on the battery. 

 

Check Charger Settings 

The chargers float and equalize voltage settings should be checked at least once a year.  The proper float and equalize settings should 
be verified at the battery terminals. 

High water consumption is usually caused by a high float voltage setting of the charger.  A high float voltage setting will force more 
current into the battery than required and the extra heat generated will cause excessive water loss. 

Seeing batteries or cells with low voltages is typical of a system that is being undercharged.  If the leads from the charger to the battery 
are long or undersized voltage drop will occur and the system will be undercharged.  To compensate for voltage drop the charger 
settings may need to be increased and checked against the battery terminals.   

 

Capacity/Discharge Testing 

Capacity testing (acceptance and performance tests) is used to trend battery aging. The result of a capacity test is a calculation of the 
capacity of the battery. The calculated capacity is used to determine whether the battery requires replacement. 

Capacity tests should be carried out in accordance with IEEE1106-2005.  

In nickel-cadmium batteries, approximately 12 weeks is needed after a previous discharge for the “float effect” to reach its full extent 
(see Annex D of IEEE1106 for details). Results of capacity tests that are carried out after less than 12 weeks have elapsed will not be 
characteristic of normal operation and the results should not be compared with future performance test results.   

Note: SBS does not recommend an acceptance or performance test until the system has been in float service for a minimum of 12 
weeks. Results of a test carried out before the system has been on float for 12 weeks will not be considered for warranty purposes. 

 

Test length 

SBS recommends discharge times of 1 to 8 hours to an end cell voltage of 1.00- 1.14 Vpc. 

For comparison purposes, having the performance test be similar in duration to the battery duty cycle and to the end voltage originally 
used for sizing is desirable. 

 

Discharge Rate 

Correct discharge rates (in amps) must be chosen from discharge rate tables based on long term float charging ratings. 

Performance data is available at 

www.sbsbattery.com

 or can be supplied by contacting SBS. For trending purposes, the same test 

length and rate should be used for each test during the batteries service life. 

 

Temperatures effect on a Capacity/Discharge Test  

Discharge tests should be performed between 65°F and 90°F.   

For tests of a duration of 1 hour or more, do not adjust the rate of the discharge.  The time adjusted capacity calculation allows you to 
factor in the temperature correction factor (Kc) after the test is completed.

 

 

Acceptance Testing 

Acceptance tests may be carried out after the battery has been on float charge for at least 12 weeks without discharging. Although an 
acceptance test carried out after less than 12 weeks on float charge will confirm that a battery has adequate capacity, the acceptance 
test results cannot be compared with future performance test results because of the “float effect” (see Annex D in IEEE1106-2005 for 
details). This condition makes performing an acceptance test that accurately reflects operation in float charging mode impractical. 

 

Performance Testing 

Per IEEE a performance test should be made within the first two years of service and at five-year intervals until the battery shows signs 
of excessive capacity loss. Annual performance tests of battery capacity should be made on any battery that shows signs of excessive 
capacity loss. SBS recommends using the time adjusted method for calculating system capacity as outlined on page 11. 

 

Summary of Contents for KBH Series

Page 1: ...parks due to shorting across cell terminals may result in an explosion of hydrogen gas in or near the cells Insulate tool handles to protect against shorting Prior to making contact with the cell disc...

Page 2: ...pc 1 45 Vpc 1 52 1 57 Vpc Charging Option B Note Boost system for 72hrs when any cells voltage falls below 1 36 volts Use Option A Boost charging voltage data Float Voltage Range 1 46 1 49 Vpc Not Rec...

Page 3: ...RRANTY NOTES Any of the following actions will invalidate the warranty Non adherence to the Installation Operating and Maintenance Instructions Repairs carried out with non approved parts or by non ap...

Page 4: ...s can be float charged during storage A filled and charged battery can be stored for a maximum period of one year If in storage for more than 6 months the battery must be discharged to an average cell...

Page 5: ...ause damage to the battery The layout and contents of a battery room must allow easy access to the batteries and must comply with all national and local codes Handling SBS Ni Cd batteries are normally...

Page 6: ...ype of lubricant such as Grease or Oil as they may contain mineral spirits which can cause crazing and cracking of the plastic jar material Make sure to arrange batteries plumb and level with the corr...

Page 7: ...72hours at a voltage of Flooded Pocket Plate Ni Cd batteries 1 54 1 69 Vpc Valve Regulated Pocket Plate Ni Cd batteries 1 45 Vpc Flooded Fibre Plate Ni Cd batteries 1 52 1 57 Vpc If after 72 hours an...

Page 8: ...ystem to correct voltage spread the charger should be set to the highest possible voltage without exceeding the voltage sensitivity of your connected load Disconnecting the load and using the highest...

Page 9: ...ty 10 S cm to top off cells Under ideal operating conditions flooded Ni Cad batteries should require watering every 6 24 months Watering intervals are influenced by temperature charging rates and the...

Page 10: ...oes not recommend an acceptance or performance test until the system has been in float service for a minimum of 12 weeks Results of a test carried out before the system has been on float for 12 weeks...

Page 11: ...result of cell reversal so no provisions are required for bypassing weak cells Reversing the polarity of NiCad cells should not be a basis for terminating a discharge test before the over all terminal...

Page 12: ...YSTEM CHECKS record in a log book the following Record the battery system float charging voltage It should be equal to the number of cells multiplied by the recommended charging voltage per cell Recor...

Reviews: