Assembly and operating instructions Type ALD1B5FS 

32 A bidirectional Single Phase active power energy meter with S-Bus interface, Pic. 1

Description

Energy meter with S-Bus interface enables the reading of all 

relevant data like meter reading, electricity, voltage, power 

(active and reactive) and cos phi.

Indicating elements (Pic. 4)

T   (kWh) 

 

Indicates the total consumption 

T   (kWh) 

 

Indicates the total feeding back 

P (kW) 

  

Indicates the instantaneous power  

Current   = consumption (pos.) 

Current   = feeding back (neg.)

U (V)  

  

Indicates the voltage 

I (A)  

 

Indicates the current 

2000 pulses/kWh  

  

Pulsates according to the amount 

of used power. 

Technical data

Connection  

  Pic. 2

diagram

Dimensions 

 

Pic. 3

Accuracy class 

 

B according to EN50470-3,  

 

 1 according to IEC62053-21

Reference, Maxi- 

 

I

ref

 = 5 A, Im

ax 

= 32 A, Ist

 =

 20 mA

mum, initial current

operating voltage 

 

230 V

AC

, 50 Hz 

 

  Tolerance −20%/+15%

Counting range 

  00 000,00…999 999,9 kWh

Connections 

 

Conductor cross-section max. 6 mm

2

,

 

Main circuit 

  screwdriver pozi no. 1, slot no. 1,  

 

  torque 1,2 Nm

Connections 

 

Conductor cross-section max. 2,5 mm

2

Control circuit 

  screwdriver pozi no. 0, slot no.1, 

 

  torque 0,5 Nm

Operating  

 

−25… +55°C (noncondensing

temperature 

  according standard EN50470)

Environment  

  Mechanical M2

 

  Electromagnetic E2

Notes before connecting 

In order to avoid moisture in the meter due to condensate 

build-up, acclimatise the meter at room temperature for 

about half an hour before connecting.

Attention!

These devices must only be installed by a professional 

electrician, otherwise there is the risk of fire or the risk of 

an electric shock.

Declaration of Conformity CE

We, Saia-Burgess Controls Ltd., CH 3280 Murten (Switzer-

land), herewith declare, on our own responsibility that 

the products:

 

 

ALD1B5FS00A3A00

which this certificate refer to, are in accordance with the 

directive 2004/22/EG (MID) and the following standards:
 

  EN50470 parts 1 and 3 (electronic meter), of  

  October 

2006. 

ESD on equipment side: 13 kV.

Murten, 30.04.2013

Conformity Assessment Body:

    METAS-Cert, Nr. 1259

  CH-3003 

Bern-Wabern 

Signed: Urs Tanner, Site Quality Leader

English

Installation instructions

The energy meter can be attached to a 35 mm rail 

(EN60715TH35). 

The meter can be used only in installation cabinets. 

Operation of the LCD display

See page with LCD menu navigation.

4 319 5139 0E  

03.2017   

Subject to change without notice

Method of operation 

Energy is added as indicated by the arithmetic operator. 

Positive output in the meter indicates that energy is being 

supplied, while negative output indicates that energy is 

being delivered.

Summary of Contents for Saia PCD ALD1B5FS

Page 1: ...0 Imp kWh Pulsiert entsprechend der bezogenen Leistung Hinweise vor dem Anschliessen Um Feuchtigkeit im Zähler durch Kondenswasser zu ver meiden den Zähler vor dem Anschliessen ca eine halbe Stunde bei Raumtemperatur akklimatisieren Achtung Diese Geräte dürfen nur durch eine Elektrofachkraft installiert werden andernfalls besteht Brandgefahr oder Gefahr eines elektrischen Schlages EG Konformitätse...

Page 2: ...ter benutzt werden Die Schnittstelle hat keinen Abschlusswiderstand dieser sollte extern bereitgestellt werden Die verwendeten Register sind in der Registerliste beschrieben Datenübertragung Nur lese schreib Register Befehle werden erkannt Es kann immer nur ein Register auf einmal beschrieben werden Das Gerät wird ein NAK zurückgeben wenn mehr als ein Register auf einmal beschrieben wird Es können...

Page 3: ...ing standard EN50470 Environment Mechanical M2 Electromagnetic E2 Notes before connecting In order to avoid moisture in the meter due to condensate build up acclimatise the meter at room temperature for about half an hour before connecting Attention These devices must only be installed by a professional electrician otherwise there is the risk of fire or the risk of an electric shock Declaration of...

Page 4: ...th more than 128 devices a repeater should be used The interface don t have a terminal resistor this must be provided external For a description of the used registers please look at the register page Data transmission Only read write register instructions are recognized Only one register can be written at the same time The device will respond NAK if more than 1 register is written Up to 10 Registe...

Page 5: ...corrente 2000 impulsi kWh Impulsi secondo l uscita indicata Dichiarazione di conformità CE Noi Saia Burgess Controls SA CH 3280 Morat Svizzera dichiarammo in nostra propria responsabilità che i prodotti ALD1B5FS00A3A00 di quali si riferisce questa dichiarazione rispondono alla direttiva 2004 22 CE MID e alle normative seguente normativa EN50470 Parte 1 e 3 Contatori elettronici Octobre 2006 ESD su...

Page 6: ...interfaccia non ha alcuna resistenza terminale questa dovrebbe essere disponibile esternamente Per una descrizione dei registri utilizzati consultare la Pagina Registri Trasmissione dei dati Vengono riconosciute solo le istruzioni read write register Può essere iscritto solo un registro alla volta L apparecchio risponderà con un NAK se viene iscritto più di un registro alla volta Possono essere le...

Page 7: ...ourant consommation pos courant récupération neg U V Tension I A Courant 2000 pulses kWh Impulsions en fonction de la puissance absorbée Déclaration de conformité CE Nous Saia Burgess Controls SA CH 3280 Morat Suisse déclarons sous notre propre responsabilité que les produits ALD1B5FS00A3A00 pour lesquels cette déclaration se référe sont conformes à la directive 2004 22 CE MID et aux normes suivan...

Page 8: ...ombre d appareils est supérieur à 128 utiliser un répéteur L interface n est pas dotée d une résistance de terminaison celle ci doit être mise à disposition de façon externe Les registres utilisés sont décrits dans la liste de registres Transfert de données Seules les instructions de type registre lecture écriture sont reconnues Un seul régistre peut être écrit à la fois L appareil renverra un sig...

Page 9: ...of wires twisted D max 1200 meters D B U V P P P kW kW kW I A 2000 Imp kWh kWh kWh ALD1B5F T T 5560 L1 N B U V P P P kW kW kW I A 2000 Imp kWh kWh kWh ALD1B5 F T T 431951390E 230 VAC 4 319 5139 0E 03 2017 Subject to change without notice ...

Page 10: ...7 x Error flags 0 No error 1 Error 18 x Not used will give 0 19 x Energy direction register 0 energy direction consumption 4 energy direction feeding back 20 x Counter total energy consumption 10 2 kWh multiplier 0 01 Ex 00912351 009123 51 kWh 21 x Counter total energy feeding back 10 2 kWh multiplier 0 01 Ex 00912351 009123 51 kWh 22 x Not used will give 0 23 x Not used will give 0 24 x Effective...

Page 11: ...Menu to display the value on LCD Start T Tariff consumption T Tariff feeding back P Instantaneous power ...

Page 12: ...Back to Start Back to Start U Voltage I Current 20 s 3 s 2 s ...

Reviews: