Saia-Burgess Controls AG
User Manual Standby System
│
Document 27-645
│
Edition E
NG 02
│
2017-04-26
Diagnostic Tags
Technical Imformation
3-2
3
3.2
Diagnostic Tags
There are some diagnostic tags which show the current state of the redundancy
system. The section name is
[SYS-Redundancy]
.
These diagnostic tags are also present in the redundancy CPU1.
Message
CFG Access Def. Min/
Max
Description
Remarks
Type
NO
Read
only
0
2
0: OFF
1: Primary PCD
2: Secondary PCD
TypeText
NO
Read
only
–
–
“OFF”
“PRIMARY”
“SECONDARY”
Same as
Type but
as text
Status
NO
Read
only
0
4
0: STARTUP
1: IDLE
2: STANDBY
3: ACTIVE - Redundancy
4: ACTIVE- Non Redundancy
StatusText
NO
Read
only
–
–
“STARTUP”
“IDLE”
“STANDBY”
“ACTIVE”
Same as
Status but
as text
StandbyOrActive
NO
Read
only
0
1
0: Standby
1: Active
Redundancy
NO
Read
only
0
1
0: No Redundancy
1: Redundancy
DataSyncOK
NO
Read
only
0
1
Data Synchronization:
0: FAILED
1: OK
ProgSyncOK
NO
Read
only
0
1
Program Synchronization
0: FAILED/Different Program
1: OK/Same Program
DataUpdateTime
NO
Read
only
0
65536
Data synchronization update time
in ms
DataSendTime
NO
Read
only
0
65536
Data synchronization send time
in ms
SetActive
NO
Write
only
0
1
1: Set this station as Active if
possible
SetStandby
NO
Write
only
0
1
1: Set this station as Standby if
possible