![SBC PCD1 Series Manual Download Page 282](http://html1.mh-extra.com/html/sbc/pcd1-series/pcd1-series_manual_1205032282.webp)
Saia-Burgess Controls AG
Manual
Manual PCD 1 / PCD 2 Series
│ Document 26
/
737 E
N22 │ 2013-11-26
Appendix
A-9
Installation direction and relays contact protection
A
The resistors used must withstand high voltages (pulse stability). With low resistance
values in particular, voltage flashovers can occur at the ground helical section pro
-
duced in the manufacturing process. For this reason, composite carbon resistors are
often used in screening units. However, enamelled wire resistors or cement resistors
with a large helical pitch are suitable.
Dimensioning guide:
The value for C is the direct result of the switching current. The resistance value R can
be established by drawing a straight line through the corresponding points on the I and U
curves and reading off the resistance at the intersection with the R curve.
Load
Example:
U = 100 V
I = 1 A
C is direct result with 0,1
μF
R = 10