Hardware manual PCD1.M2220-C15 │ Document 27-640 – Version ENG03 │ 2020-03-25
Saia-Burgess Controls AG
On-board | Analogue inputs
Inputs/outputs (I/O)
6-7
6
Programming
Definition for range, over range, under range and status flag:
Temperature inputs:
Type
min./max. Status flag
Range values
Pt 1000 (–50… 400°C)
–500
/
4000
Limits –500… 4000
Ni 1000 (–50… 210°C)
–500
/
2100
Limits –500… 2100
Ni 1000 L&S (–30… 140°C)
–300
/
1400
Limits –300… 1400
–10 ... + 10V
–12
/
+ 12
Limits –10100…10100
0 ... 2500 Ω
0
/
25500
Limits 0…25500
0 ... 7500 Ω
0
/
7650
Limits 0… 7650
0 ... 300 kΩ
0
/
30600
Limits 0… 30600
Each time the min./max. values are reached, the min./max. status flag is set.
100%
2%
2%
under
range
over
range
value
min. value
XX
max. value
YY
The status flag remains set until the status has been read.