These products should not be fitted to PIR circuits or short duration timed switches.
Install in accordance with the IEE Wiring regulations and current Building
Regulations.
This light fitting is double insulated and does
not require connection to an Earth circuit.
Plan the desired layout of these fittings carefully, ensuring the cables will reach the distances between each light fitting.
Avoid locating any cables in positions that would cause a hazard. Position cables away from areas where they may be
at risk from being cut, trapped or damaged
The mains supply cable must have a minimum cross section area of 1.0mm
2
.
This product is designed to be fitted into a suspended ceiling or wall mounted.
This product has special protection against the ingress of moisture and is IP65 rated.
220-240V~, 50Hz
Supply
Voltage:
The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole
luminaire shall be replaced.
Conformity with all relevant EC Directive requirements.
The power supply is Double Insulated and does not require connection to an Earth circuit.
Waste electrical products should not be disposed of with household waste. Please recycle where facilities
exist. Check with your Local Authority or local store for recycling advice.
Any faulty, broken or damaged modules should be replaced immediately.
Waste electrical products should not be disposed of with household waste. Please
recycle where facilities exist. Check with your local authority or retailer for
recycling advice.
Do not use Megger or similar high voltage instruments. Due to the fact this
Emergency pack contains electronic components that maybe damaged by high test
voltages, they must be disconnected from the circuit before testing.
To prevent damage to the Emergency pack, do not mix with conventional magnetic
ballasts on the same electrical circuit.
Please read these instructions carefully before commencing any work
This unit must be fitted by a competent and qualified electrician.
Check the pack and make sure you have all the parts listed.
To prevent electrocution switch off at the mains supply before installing or
maintaining this fitting. Ensure other persons cannot restore the electrical
supply without your knowledge.
This light fitting should be connected to a fused circuit.
If replacing an existing fitting, make a careful note of the connections.
This product is not suitable for dimming.
Existing fittings must be completely removed before installation of a new product. Before removing the existing fitting, carefully
note the position of each set of wires.
Note that the switch is turned off before installation.
After deciding the layout of the light fittings ensure that the cables are long enough to connect to desired positions.
Bulb
Type:
4.5W LED (SMD), 6500K
Duration:
3 hours (180 minutes)
Operating Temperature
: -20ºC to 45ºC
Maximum Operatin Humidity:
10-90%
This product is rated at IP65.
IP
65
Change over Time:
Approximately 1s
Battery Specification:
LiFePO4 3.2V 1500mAh
Battery Charge Time:
24 hours
Battery warranty:
2 years
This product is rated at IK08.
IK
08
• Undo two screws at the end of the product then pushing the two quick release tabs on the one side of the front cover to
separate the rear casing from product. Keep screws in safe place for refitting later.
• Choose the cable entry holes on the rear casing and drill out the conduit knockouts accordingly.
• This unit can be mounted on the wall or ceiling. After deciding the mounted way accordingly, Using the rear casing as a
template mark the position to drill out the fixing holes. Take care to avoid damaging any concealed wiring and pipes.
The correct fixings should be used, depending upon the surface to be mounted.
• Fix the rear casing into the position with the installation plugs and screws (supplied).
• Pull the cable through the cable entry hole and seal to maintain the IP rating. Wire as detailed Wiring Diagram and plug battery pack into the circuit board.
Warning
Thank you for purchasing this light fitting. Please read the instructions carefully before use to ensure safe and satisfactory
operation of this product. Please retain these instructions for future reference.
Layout
Installation
Technical data
• Re-clip the front panel in place and re-secure the diffuser using the screws. Ensure that the seal is correctly fitted.
• Replace fuse or circuit breaker and switch on. Your light is now ready for use.
See Wiring diagram
1
4
5
2
3
6
7
Plug battery pack
into the circuit board
Conformity with all relevant UKCA Directive requirements.