14
Note: When setting the 8-00 parameter, it must be slowly increased from small until sufficient braking torque is
obtained, but it should not exceed the rated motor.
9. Communications Parameters
Set during running available
Parameter
Parameter functions
Setting range
Factory
setting
9-00
Communication address
1 to 247
1
9-01
Communication transmitting
speed
0: Baud rate 4800 bps
1: Baud rate 9600 bps
2: Baud rate 14400 bps
3: Baud rate 19200 bps
4: Reserved
1
9-02
Transmitting fault treatment
0: Warning and running continuously
1: Warning and deceleration to stop
2: Warning and coasting to a stop
3: No warning and running continuously
0
9-03
No-response error detection
time
0: Not detected
1-20: 1 to 20s
0
9-04
Communications format 1
ASCII mode
0: ASSII mode <8, N,1>
1: ASSII mode <8, N,2>
2: ASSII mode <8, E,1>
3: ASSII mode <8, E,2>
4: ASSII mode <8, O,1>
5: ASSII mode <8, O,2>
6: RTU mode <8, N,2>
7: RTU mode <8, E,1>
8: RTU mode <8, O,1>
0
Communications format 2
RTU mode